Operating instructions

R3G560-AG07-03

Translation of the original operating instructions

4.5 Connection screen

No.

Conn.

Designation

Function / assignment

PE

PE

Protective earth connection

KL1

1, 2, 3

L1, L2, L3

Supply voltage, 50/60 Hz

KL2

1

NC

Floating status message contact, normally closed connection

KL2

2

COM

Floating status message contact, changeover contact, common connection (2 A, max. 250 VAC,
min. 10 mA, AC1)

KL2

3

NO

Floating status message contact, normally open connection

KL3

1

OUT

Analog output, 0-10 VDC, max. 3 mA, SELV,
output of the current level control coefficient:
1 V equates to 10 % level control coefficient.
10 V equate to 100 % level control coefficient.

KL3

2, 8

GND

Reference mass for control interface, SELV

KL3

3, 7

0-10 V

Use control / actual value input 0-10 VDC, impedance 100 kΩ only as alternative to 4-20 mA input, SELV

KL3

4

+10 V

Voltage output 10 VDC (+/-3 %), max. 10 mA, supply voltage for ext. devices
(e.g. potentiometers), SELV

KL3

5

+20 V

Voltage output 20 VDC (+25 %/-10 %), max. 50 mA, supply voltage for ext. devices
(e.g. sensors), SELV

KL3

6

4-20 mA

Use control / actual value input 4-20 mA, impedance 100 Ω, only as alternative to 0-10 V input, SELV

KL3

9, 11

RSB

RS485 interface for ebmBus, RSB, SELV

KL3

10, 12

RSA

RS485 interface for ebmBus, RSA, SELV

Item no. 50151-5-9970 · Revision 82539 · Release 2014-05-08 · Page 9 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for R3G560-AG07-03

Page 1: ...ce to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it i...

Page 2: ...g on the system machine wait until all parts have come to a standstill DANGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing...

Page 3: ...imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation with external vibrations Moving solids content in flow medium Pai...

Page 4: ...g torque 4 0 6 Nm 2 Accessory part Inlet nozzle 63071 2 4013 not included in delivery other inlet nozzles on request 3 Depth of screw max 25 mm 4 Tightening torque terminal box cover 3 5 0 5 Nm Item n...

Page 5: ...peration mode S1 Motor bearing Ball bearing Technical features Output 10 VDC max 10 mA Output 20 VDC max 50 mA Output for slave 0 10 V Input for sensor 0 10 V or 4 20 mA Alarm relay Integrated PID con...

Page 6: ...s must no longer be installed Install the undamaged device according to your application 4 2 Connecting the electrical system DANGER Electric voltage on the device Electric shock Always install a prot...

Page 7: ...VAC 16 A 15 A C16A 1 5 16 3 PE AC 380 480 VAC 20 A 20 A C20A 2 5 14 3 PE AC 380 480 VAC 25 A 25 A C25A 4 0 12 3 PE AC 380 480 VAC 32 A 30 A C32A 6 0 10 AWG American Wire Gauge 4 2 3 Idle current Beca...

Page 8: ...se a screwdriver to do so During the connection work ensure that no cables splice off Fig 2 Connecting the wires to terminals Seal the terminal box 4 3 3 Cable routing No water may penetrate along the...

Page 9: ...quate to 100 level control coefficient KL3 2 8 GND Reference mass for control interface SELV KL3 3 7 0 10 V Use control actual value input 0 10 VDC impedance 100 k only as alternative to 4 20 mA input...

Page 10: ...remove any that are found Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4 8 Switching off the device Switching off the device during operation Switch of...

Page 11: ...ge Switch off de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The error message resets automatically The device starts...

Page 12: ...ainst accidental contact for damage and to ensure that it is intact Visual inspection At least every 6 months Repair or replacement of the device Check the device for damage to blades and housing Visu...

Reviews: