Translation of the original operating instructions

4.5 Connection diagram

Drawing preliminary!

No.

Conn.

Designation

Function/assignment

KL 1

1

L1

Supply connection, power supply, phase, see nameplate for voltage range

KL 1

2

L2

Supply connection, power supply, phase, see nameplate for voltage range

KL 1

3

L3

Supply connection, power supply, phase, see nameplate for voltage range

PE

PE

Ground connection, PE connection

KL 2

1

NO

Status relay, floating status contact, make for failure

KL 2

2

COM

Status relay, floating status contact, changeover contact, common connection, contact rating, max. 250 VAC/2
A (AC1)/min. 10 mA

KL 2

3

NC

Status relay, floating status contact, break for failure

KL 3

1

RSA

Bus connection RS485, RSA, MODBUS RTU; SELV

KL 3

2

RSB

Bus connection RS485, RSB, MODBUS RTU; SELV

KL 3

3 / 10

GND

Reference ground for control interface, SELV

KL 3

4

Ain1 U

Analog input 1, set value: 0-10 V, Ri = 100 kΩ, adjustable curve, only usable as alternative to input Ain1 I;
SELV

KL 3

5

+ 10 V

Fixed voltage output 10 VDC, +10 V ± 3%, max. 10 mA, short-circuit-proof, power supply for external
devices (e.g. pot); SELV

Item no. 54671-5-9970 · ENU · Change 260759 · Approved 2022-06-28 · Page 11 / 16

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for R3G450-PB24-01

Page 1: ...permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the devic...

Page 2: ...come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and cause injuries Take appropriate safety measures WARNING Rotatin...

Page 3: ...e In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation...

Page 4: ...luded in scope of delivery 2 Max clearance for screw 25 mm 3 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 4 Cable diameter min 9 mm max 16 mm tightening torque 6 0 9 Nm 5 Tightening to...

Page 5: ...All dimensions in mm Inlet ring 45075 2 4013 with pressure tap k factor 240 Item no 54671 5 9970 ENU Change 260759 Approved 2022 06 28 Page 5 16 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mul...

Page 6: ...d from ebm papst If other air conduction geometries are used on the installation side the ebm papst evaluation loses its validity the conformity must be confirmed again The product does not fall withi...

Page 7: ...er than or equal to 120 times the rated output of the arrangement It is the responsibility of the installation engineer or operator owner of the device to ensure if necessary after consultation with t...

Page 8: ...an additional protective earth conductor by way of the extra protective earth terminal provided on the device The protective earth terminal is located on the housing and provided with a protective ea...

Page 9: ...t included in scope of delivery into the terminal box First connect the PE protective earth Connect the wires to the corresponding terminals Use a screwdriver to do so When connecting ensure that no w...

Page 10: ...eter set 2 PWM control Fan device address 01 Max PWM 100 Min PWM 5 Save set value to EEPROM Yes Set value requirement Analog linear Direction of action parameter set 1 Positive heating Direction of ac...

Page 11: ...ngeover contact common connection contact rating max 250 VAC 2 A AC1 min 10 mA KL 2 3 NC Status relay floating status contact break for failure KL 3 1 RSA Bus connection RS485 RSA MODBUS RTU SELV KL 3...

Page 12: ...er according to EEPROM setting the direction of action of the integrated controller can be selected as normal inverse via bus or digital input Normal Pin open or applied voltage 5 50 VDC Inverse Bridg...

Page 13: ...ng Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessively high vibration levels can lead to premature failure The maximum per...

Page 14: ...e from supply and remove mechanical blockage Line voltage faulty Check line voltage restore power supply Attention The error message resets automatically Device restarts automatically without warning...

Page 15: ...aintenance intervals to the actual level of dust exposure 6 3 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testing volta...

Page 16: ...tallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plasti...

Reviews: