4.4 Connection screen

No.

Conn. Designation

Colour

Function / assignment

CON10 L

black

Power supply 230 VAC, 50-60 Hz, for voltage range refer to rating plate

CON11 N

blue

Neutral conductor

CON12 PE

green/
yellow

Protective earth

1

GND

blue

GND - Connection for control interface

2

0- 10V PWM

yellow

Control input 0 - 10 V or PWM, electrically isolated

3

10V/ max 1.1mA

red

Voltage output 10 V / 1.1 mA, electrically isolated, not short-circuit-proof, Isink = 10 mA

4

Tach

white

Tach output: open collector, 1 pulse per revolution, electrically isolated, Isink max = 10 mA

Item no. 51761-5-9970 · Revision 76115 · Release 2012-02-29 · Page 7 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for R3G355-RB03-03

Page 1: ...uthorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards...

Page 2: ...t the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental con...

Page 3: ...the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving highl...

Page 4: ...tandard scope of delivery other inlet nozzles on request 2 Depth of screw max 10 mm 3 Depth of screw max 10 mm 4 Connection line AWG20 3x brass lead tips crimped 5 Connection line AWG22 4x brass lead...

Page 5: ...ass B Humidity class F3 1 Mounting position Any Condensate discharge holes None open rotor Cooling bore aperture Rotor side Operation mode S1 Motor bearing Ball bearing Technical features Output 10 VD...

Page 6: ...ing switch 4 2 1 Prerequisites Check whether the data on the type plate agree with the connection data Before connecting the device ensure that the supply voltage matches the operating voltage of the...

Page 7: ...e GND Connection for control interface 2 0 10V PWM yellow Control input 0 10 V or PWM electrically isolated 3 10V max 1 1mA red Voltage output 10 V 1 1 mA electrically isolated not short circuit proof...

Page 8: ...the nominal voltage to the voltage supply Start the device by changing the input signal 4 7 Switching off the device Switching off the device during operation Switch off the device via the control inp...

Page 9: ...ise correct connection see connection diagram Overtemperature of electronics motor Insufficient cooling Improve cooling Let the device cool down To reset the error message switch off the mains supply...

Page 10: ...the wires for damage Visual inspection At least every 6 months Replace wires Impeller for wear deposits corrosion and damage Visual inspection At least every 6 months Clean or replace impeller Item n...