ebm-papst R3G310-RP04-B1 Operating Instructions Manual Download Page 2

Operating instructions

R3G310-RP04-B1

Translation of the original operating instructions

CAUTION
In the event of failure, there is electric voltage at the
rotor and impeller

The rotor and impeller are base insulated.
→ Do not touch the rotor and impeller once they are installed.

CAUTION
If control voltage is applied or a speed setpoint is stored,
the motor automatically restarts, e.g. after a power failure.

Danger of injury
→ Keep out of the danger zone of the device.
→ When working on the device, switch off the mains

supply voltage and secure the latter from being switched on
again.

→ Wait until the device stops.
→ After working on the device, remove any used tools or

other objects from the device.

1.5 Safety and protective functions

DANGER
Missing safety device and non-functioning safety device

If there is no safety device, you could be seriously injured, for
example if you reach into the running device or your hands are
sucked into it.
→ Operate the device only with a fixed and isolating safety

protection and a fixed guard grille.
The guard must withstand the kinetic energy of a fan blade
detaching at maximum speed.

→ The device is a built-in component. You, the owner/

operator, are responsible for providing adequate protection for
the device.

→ Shut down the device immediately if you detect a

missing or ineffective protective feature.

1.6 Electromagnetic radiation

Interference from electromagnetic radiation is possible, e.g. in conjunction
with open and closed-loop control devices.
If unacceptable emission intensities occur when the fan is installed,
appropriate shielding measures have to be taken by the user.

NOTE
Electrical or electromagnetic interferences after
integrating the device in installations on the customer's
side.

→ Verify that the entire setup is EMC compliant.

1.7 Mechanical movement

DANGER
Rotating device

Body parts that come into contact with the rotor and impeller
can be injured.
→ Secure the device against accidental contact.
→ Before working on the system/machine, wait until all

parts have come to a standstill.

WARNING
Rotating device

Long hair, loose items of clothing and jewellery could become
entangled and pulled into the device. You could be injured.

→ Do not wear any loose clothing or jewellery while working

on rotating parts.

→ Protect long hair by wearing a cap.

1.8 Emission

WARNING
Depending on the installation and operating conditions,
a sound pressure level greater than 70 dB(A) may arise.

Danger of noise-induced hearing loss
→ Take appropriate technical safety measures.
→ Protect operating personnel with appropriate safety

equipment, e.g. hearing protection.

→ Also observe the requirements of local agencies.

1.9 Hot surface

CAUTION
High temperature at the electronics enclosure

Danger of burn injuries
→ Ensure that sufficient protection against accidental contact is

provided.

1.10 Storage

;

Store the device, partially or fully assembled, in a dry and
weatherproof manner in the original packing in a clean environment.

;

Protect the device from environmental impacts and dirt until the final
installation.

;

We recommend storing the device for a maximum up to one year to
guarantee proper operation and longest possible service life.

;

Even devices explicitly suited for outdoor use are to be stored as
described prior to being commissioned.

;

Maintain the storage temperature, see
chapter 3.6 Transport and storage conditions.

;

Please make sure that all screwed cable glands are fitted with
dummy plugs.

1.11 Disposal

When disposing of the device, please comply with all relevant
requirements and regulations applicable in your country.

Item no. 51760-5-9970 · Revision 82624 · Release 2014-05-08 · Page 2 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for R3G310-RP04-B1

Page 1: ...mitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must...

Page 2: ...7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the system mach...

Page 3: ...particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Opening the terminal box during operation Moving air that contains abrasive p...

Page 4: ...000 2 4013 not included in the standard scope of delivery 2 Depth of screw max 16 mm 3 Cable diameter min 4 mm max 10 mm tightening torque 2 5 0 4 Nm 4 Tightening torque 3 5 0 5 Nm Item no 51760 5 997...

Page 5: ...ion mode S1 Motor bearing Ball bearing Technical features Output 10 VDC max 10 mA Output 20 VDC max 50 mA Output for slave 0 10 V Input for sensor 0 10 V or 4 20 mA Alarm relay Motor current limit PFC...

Page 6: ...ectrical voltage The fan is a built in component and features no electrically isolating switch Only connect the fan to circuits that can be switched off with an all pole separating switch When working...

Page 7: ...on Strip the cable just enough so that the screwed cable gland is tight and the terminals are relieved of strain Tightening torque see chapter 3 1 Product drawing Fig 1 Recommended stripping lengths i...

Page 8: ...er set 2 PWM controlling Fan device adress 01 Max PWM 98 Min PWM 8 0 Save set value to EEPROM Yes Set value control Analogue linear Control function parameter set 1 Positive heating Control function p...

Page 9: ...V correspond to 100 level control coefficient KL3 2 8 GND Reference mass for control interface SELV KL3 3 7 0 10 V Use control actual value input 0 10 VDC impedance 100 k only as alternative to 4 20...

Page 10: ...nal damage and the proper function of the protective features before switching it on Check the air flow paths of the fan for foreign objects and remove any that are found Apply the nominal voltage to...

Page 11: ...ector responded Allow motor to cool off locate and rectify cause of error if necessary cancel restart lock out Overtemperature of electronics motor Insufficient cooling Improve cooling Let the device...

Page 12: ...eposits corrosion and damage Visual inspection At least every 6 months Clean or replace impeller Tightness of screwed cable gland Visual inspection At least every 6 months Retighten replace if damaged...

Reviews: