background image

Operating instructions

R3G280-PS10-J1

Translation of the original operating instructions

4.5 Connection diagram

Drawing preliminary!

No.

Conn.

Designation

Color

Function/assignment

1

1, 2

PE

green/
yellow

Protective earth

1

3

L1

black

Power supply

1

4

L2

black

Power supply

1

5

L3

black

Power supply

1

6

NC

white 1

Status relay, floating status contact, break for failure,
contact rating 250 VAC / 2 A (AC1) / min. 10 mA; reinforced insulation on supply side and basic
insulation on control interface side

1

7

COM

white 2

Status relay, floating status contact, break for failure,
contact rating 250 VAC / 2 A (AC1) / min. 10 mA; reinforced insulation on supply side and basic
insulation on control interface side

2

8

0-10V

yellow

Analog input (set value), 0-10 V, Ri = 100 kΩ, adjustable curve, SELV

2

10

RSB

brown

RS485 interface for MODBUS, RSB; SELV

2

11

RSA

white

RS485 interface for MODBUS, RSA; SELV

2

12

GND

blue

Reference ground for control interface, SELV

2

13

+10V

red

Fixed voltage output 10 VDC, +10 V ±3%, max. 10 mA, short-circuit-proof power supply for
external devices (e.g. pot), SELV
fixed voltage input 24 VDC for setting parameters via MODBUS without line voltage supply

Item no. 54447-5-9970 · ENU · Change 211277 · Approved 2020-02-07 · Page 9 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for R3G280-PS10-J1

Page 1: ...are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the de...

Page 2: ...y that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accide...

Page 3: ...instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice form...

Page 4: ...13 with pressure tap k factor 77 not included in scope of delivery 2 Max clearance for screw 16 mm 3 Cable PVC AWG18 6x crimped ferrules 4 Cable PVC AWG22 5x crimped ferrules Item no 54447 5 9970 ENU...

Page 5: ...zed measurement setup 3 4 Technical description Weight 5 4 kg Size 280 mm Motor size 84 Rotor surface Painted black Impeller material PP plastic Housing material Die cast aluminum Number of blades 6 D...

Page 6: ...t is the responsibility of the installation engineer or operator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected to a connect...

Page 7: ...al protective earth conductor by way of the extra protective earth terminal provided on the device The protective earth terminal is located on the housing and provided with a protective earth symbol a...

Page 8: ...ade for the device by ebm papst Mode parameter set 1 PWM control Mode parameter set 2 PWM control Fan device address 01 Max PWM 100 Min PWM 5 Save set value to EEPROM Yes Set value requirement Analog...

Page 9: ...g 250 VAC 2 A AC1 min 10 mA reinforced insulation on supply side and basic insulation on control interface side 2 8 0 10V yellow Analog input set value 0 10 V Ri 100 k adjustable curve SELV 2 10 RSB b...

Page 10: ...issible vibration severity must not exceed 3 5 mm s and should be checked at intervals of 6 months It is to be determined at the motor mount at the motor support plate at least in axial direction and...

Page 11: ...eck line voltage restore power supply Attention The error message resets automatically Device restarts automatically without warning Faulty connection Isolate from supply correct connection see connec...

Page 12: ...e maintenance intervals to the actual level of dust exposure 6 3 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testing vo...

Page 13: ...tallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plasti...

Reviews: