ebm-papst R3G250-RE09-09 Operating Instructions Manual Download Page 7

Operating instructions

R3G250-RE09-09

Translation of the original operating instructions

3.5 Mounting data

Strength class of
screws

8.8

For screw clearance, see Chapter 3.1 Product drawing

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

Any further mounting data required can be taken from the product
drawing or Section Chapter 4.1 Mechanical connection.

3.6 Transport and storage conditions

Max. permitted
ambient temp. for
motor (transport/
storage)

+ 80 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

- 40 °C

4. CONNECTION AND STARTUP

4.1 Mechanical connection

CAUTION
Cutting and crushing hazard when removing fan from
packaging

→ Carefully remove the device from its packaging, by the fan

impeller. Strictly avoid shocks.

→ Wear safety shoes and cut-resistant safety gloves.

NOTE
Damage to the device from vibration

Bearing damage, shorter service life
→ The fan must not be subjected to force or excessive vibration

from sections of the installation.

→ If the fan is connected to air ducts, the connection should

be isolated from vibration, e.g. using compensators or similar
elements.

→ Ensure stress-free attachment of the fan to the

substructure.

;

Check the device for transport damage. Damaged devices are not to
be installed.

;

Install the undamaged device in accordance with your application.

CAUTION
Possible damage to the device

If the device slips during installation, serious damage can result.
→ Ensure that the device is securely positioned at its place of

installation until all fastening screws have been tightened.

The fan must not be strained on fastening.

4.2 Electrical connection

DANGER
Voltage on the device

Electric shock
→ Always connect a protective earth first.
→ Check the protective earth.

DANGER
Faulty insulation

Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation

regulations for voltage, current, insulation material, capacity,
etc.

→ Route cables so that they cannot be touched by any

rotating parts.

DANGER
Electrical charge (>50 µC) between phase conductor and
protective earth connection after switching off supply
with multiple devices connected in parallel.

Electric shock, risk of injury
→ Ensure sufficient protection against accidental contact.

Before working on the electrical hookup, short the supply
and PE connections.

CAUTION
Voltage

The fan is a built-in component and has no disconnecting switch.
→ Only connect the fan to circuits that can be switched off with

an all-pole disconnection switch.

→ When working on the fan, secure the system/machine in

which the fan is installed so as to prevent it from being
switched back on.

NOTE
Water ingress into wires or cables

Water ingress at the customer end of the cable can damage the
device.
→ Make sure the end of the cable is connected in a dry

environment.

Only connect the device to circuits that can be switched off with
an all-pole disconnection switch.

4.2.1 Requirements

;

Check whether the information on the nameplate matches the
connection data.

;

Before connecting the device, make sure the power supply matches
the device voltage.

;

Only use cables designed for the current level indicated on the
nameplate.
For determining the cross-section, note the sizing criteria according
to EN 61800-5-1. The protective earth must have a cross-section
equal to or greater than that of the phase conductor.
We recommend the use of 105 °C cables. Ensure that the minimum
cable cross-section is at least
AWG 26 / 0.13 mm².

Item no. 54895-5-9970 · ENU · Change 204653 · Approved 2020-04-24 · Page 7 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for R3G250-RE09-09

Page 1: ...chnical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules...

Page 2: ...y that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accide...

Page 3: ...prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration...

Page 4: ...13 not included in scope of delivery 2 Max clearance for screw 5 mm 3 Max clearance for screw 10 mm 4 Cable PVC AWG20 3x crimped splices 5 Cable PVC AWG22 4x crimped splices Item no 54895 5 9970 ENU C...

Page 5: ...nsions in mm Accessory part inlet ring 96359 2 4013 not included in scope of delivery Item no 54895 5 9970 ENU Change 204653 Approved 2020 04 24 Page 5 12 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D...

Page 6: ...ller material PA plastic Number of blades 7 Direction of rotation Clockwise viewed toward rotor Degree of protection IP54 Insulation class B Moisture F Environmental H protection class H1 Installation...

Page 7: ...arth DANGER Faulty insulation Risk of fatal injury from electric shock Use only cables that meet the specified installation regulations for voltage current insulation material capacity etc Route cable...

Page 8: ...esidual current device RCD is required in your installation only pulse current sensitive and or AC DC sensitive residual current devices type A or B are permissible As with variable frequency drives r...

Page 9: ...12 PE green yellow Ground connection 2 0 10V PWM yellow 0 10 V PWM control input Ri 100 k SELV 4 Tach white Tach output open collector 1 pulse per revolution Isink max 10 mA SELV 3 10 V red Fixed volt...

Page 10: ...g in cyclic operation on and off via power supply Disconnect the device from the power supply When disconnecting be sure to disconnect the ground connection last 5 INTEGRATED PROTECTIVE FEATURES The...

Page 11: ...ned for a service life of 40 000 hours If bearing replacement is necessary after that period contact ebm papst Adapt the maintenance intervals to the actual level of dust exposure 6 2 Safety inspectio...

Page 12: ...num Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Onl...

Reviews: