background image

Operating instructions

R3G250-RE09-05

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G055-DF

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 240

Frequency / Hz

50/60

Type of data definition

ml

Speed / min

-1

2510

Power input / W

170

Current draw / A

1.4

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

+60

ml = max. load · me = max. efficiency · fa = running at free air

cs = customer specs · cu = customer unit

Subject to alterations

3.3 Data according to ErP directive

Installation category

A

Efficiency category

Static

Variable speed drive

Yes

Specific ratio

*

1.00

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

60.1

39.4

43.4

Efficiency grade N

78.7

58

62

Power input P

ed

/ kW

0.17

Air flow q

v

/ m³/h

1005

Pressure increase total p

sf

/ Pa

322

Speed n / min

-1

2555

Data established at point of optimum efficiency

3.4 Technical features

Mass

1.78 kg

Size

250 mm

Surface of rotor

Thick layer passivated

Material of electronics
housing

Die-cast aluminium

Material of impeller

Plastic PA6, fibreglass-reinforced

Number of blades

7

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP 54

Insulation class

"B"

Mounting position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensate discharge
holes

None, open rotor

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Speed adjustment input (230 V)
- Motor current limit
- Soft start
- Over-temperature protected
electronics / motor

Speed steps

2

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Motor protection

Locked-rotor protection

Cable exit

Variable

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 60335-1

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

For depth of screw, see chapter 3.1 Product drawing

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

;

Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+ 80 °C

Min. permissible
ambient motor temp.
(transp./storage)

- 40 °C

Item no. 51035-5-9970 · Revision 77287 · Release 2012-04-04 · Page 5 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for R3G250-RE09-05

Page 1: ...sed specialist personnel are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards s...

Page 2: ...ire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Befo...

Page 3: ...the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving highl...

Page 4: ...le 96359 2 4013 not included in the standard scope of delivery 2 Connection line PVC 4G 0 5 mm 4 x brass lead tips crimped 3 Depth of screw max 5 mm 4 Depth of screw max 10 mm Item no 51035 5 9970 Rev...

Page 5: ...n Shaft horizontal or rotor on bottom rotor on top on request Condensate discharge holes None open rotor Operation mode S1 Motor bearing Ball bearing Technical features Speed adjustment input 230 V Mo...

Page 6: ...ing switch 4 2 1 Prerequisites Check whether the data on the type plate agree with the connection data Before connecting the device ensure that the supply voltage matches the operating voltage of the...

Page 7: ...60 Hz see type plate for voltage range CON 11 N blue Neutral conductor CON 12 PE green yellow Protective earth CON 70 SL brown Speed selection switch open speed 1 switch closed speed 2 Item no 51035 5...

Page 8: ...Check the air flow paths of the fan for foreign objects and remove any that are found Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4 7 Switching off t...

Page 9: ...iagram Overtemperature of electronics motor Insufficient cooling Improve cooling Let the device cool down To reset the error message switch off the mains supply voltage for a min of 25 s and switch it...

Page 10: ...Clean or replace impeller Check the ball bearings to ensure they are quiet can move easily and are free of play Manual check by turning the rotor in shut off state At least every 6 months Replace devi...

Reviews: