ebm-papst R3G250-AP06-71 Operating Instructions Manual Download Page 5

Operating instructions

R3G250-AP06-71

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G084-DF

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 277

Frequency / Hz

50/60

Method of obtaining
data

ml

Speed (rpm) / min

-1

3350

Power consumption / W

480

Current draw / A

3.0

Max. ambient
temperature / °C

40

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to Commission Regulation (EU) 327/
2011

Actual

Req. 2015

01 Overall efficiency η

es

/ %

57.6

48.4

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

71.2

62

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart ·
HRA 590344
D-74673 Mulfingen

08 Type

R3G250-AP06-71

09 Power consumption P

ed

/ kW

0.5

09 Air flow q

v

/ m³/h

1350

09 Pressure increase total p

sf

/

Pa

702

10 Speed (rpm) n / min

-1

3310

11 Specific ratio

*

1.01

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller

combination in a standardized measurement setup.

3.4 Technical description

Weight

4.4 kg

Size

250 mm

Motor size

84

Rotor surface

Painted black

Electronics housing
material

Die-cast aluminum

Impeller material

Sheet aluminum

Number of blades

6

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP54

Insulation class

"B"

Moisture (F) /
Environmental (H)
protection class

H1

Installation position

Shaft horizontal or rotor on top; rotor on
bottom on request

Condensation
drainage holes

None

Mode

S1

Motor bearing

Ball bearing

Technical features

- Control input 0-10 VDC / PWM
- Output 10 VDC max. 1.1 mA
- Alarm relay
- Thermal overload protection for motor

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Motor protection

Thermal overload protector (TOP)
internally connected

with cable

Variable

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 61800-5-1; CE

Approval

UL 1004-3 + 60730-1; EAC; CSA
C22.2 No. 77 + CAN/CSA-E60730-1

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. This does not however in any way affect the
technical properties of the products. The product is to be protected against
UV radiation to prevent the formation of patches and fading. Changes in
color are not a reason for complaint and are not covered by the warranty.

Item no. 50055-5-9970 · ENU · Change 211950 · Approved 2020-09-21 · Page 5 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for R3G250-AP06-71

Page 1: ...authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards...

Page 2: ...nstalling the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor...

Page 3: ...prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration...

Page 4: ...t ring 25002 2 4013 not included in scope of delivery other inlet rings on request 2 Cable 5x AWG18 3 Cable 3x AWG22 4 Clearance for screw min 8 mm max 10 mm Item no 50055 5 9970 ENU Change 211950 App...

Page 5: ...erial Die cast aluminum Impeller material Sheet aluminum Number of blades 6 Direction of rotation Clockwise viewed toward rotor Degree of protection IP54 Insulation class B Moisture F Environmental H...

Page 6: ...uld be isolated from vibration e g using compensators or similar elements Ensure stress free attachment of the fan to the substructure Check the device for transport damage Damaged devices are not to...

Page 7: ...n and immunity to interference reactive currents can be measured in the supply line even when the motor is at a standstill and the line voltage is switched on The values are typically in the range 250...

Page 8: ...ting instructions 4 4 Connection diagram Drawing preliminary Item no 50055 5 9970 ENU Change 211950 Approved 2020 09 21 Page 8 11 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49...

Page 9: ...ound connection last 5 INTEGRATED PROTECTIVE FEATURES The integrated protective functions cause the motor to switch off automatically in the event of the faults described in the table Fault Safety fea...

Page 10: ...n that will shorten the service life of the fan Severe vibration can destroy the fan In such cases switch off the fan immediately and clean it The preferred method of cleaning is dry cleaning e g usin...

Page 11: ...lified personnel with the appropriate technical knowledge The product is to be disassembled into suitable components for disposal employing standard procedures for motors WARNING Heavy parts of the pr...

Reviews: