Operating instructions

R3G250-AH52-01

Translation of the original operating instructions

Mounting of
protective
earth connection

Visual inspection At least every

6 months

Fasten

Check the
insulation of
the wires for
damage

Visual inspection At least every

6 months

Replace wires

Impeller for
wear/deposits/
corrosion and
damage

Visual inspection At least every

6 months

Clean or
replace impeller

Check the ball
bearings to
ensure they
are quiet, can
move easily
and are free of
play

Manual check
by turning the
rotor in shut-off
state

At least every
6 months

Replace
device in case
of noise,
difficulty of
movement or
clearance of
the bearings

Item no. 50963-5-9970 · Revision 72864 · Release 2011-02-18 · Page 10 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for R3G250-AH52-01

Page 1: ...sonnel are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the d...

Page 2: ...ire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Befo...

Page 3: ...the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving highl...

Page 4: ...ncluded in the standard scope of delivery other inlet nozzles on request 4 Depth of screw 8 10 mm tightening torque 2 5 0 2 Nm gluing the screws is recommended 5 Pilot hole prepared for self tapping s...

Page 5: ...g Ball bearing Technical features Output 10 VDC max 1 1 mA Tach output Motor current limit Soft start Control input 0 10 VDC PWM Over temperature protected electronics motor Touch current acc IEC 6099...

Page 6: ...ing switch 4 2 1 Prerequisites Check whether the data on the type plate agree with the connection data Before connecting the device ensure that the supply voltage matches the operating voltage of the...

Page 7: ...8 0 10 V PWM yellow Control input 0 10 V or PWM electrically isolated 9 Tach white Tach output open collector 1 pulse per revolution electrically isolated 11 10V max 1 1 mA red Voltage output 10 V ma...

Page 8: ...e device by changing the input signal 4 7 Switching off the device Switching off the device during operation Switch on the device via the control input Do not switch the motor e g in cyclic operation...

Page 9: ...tector responded Allow motor to cool off locate and rectify cause of error if necessary cancel restart lock out Overtemperature of electronics motor Insufficient cooling Improve cooling Let the device...

Page 10: ...ge Visual inspection At least every 6 months Clean or replace impeller Check the ball bearings to ensure they are quiet can move easily and are free of play Manual check by turning the rotor in shut o...