background image

Operating instructions

R3G190-AF50-01

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G074-BF

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 277

Frequency / Hz

50

Type of data definition

fa

Speed / min

-1

3900

Power input / W

135

Current draw / A

1.0

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

60

ml = max. load · me = max. efficiency · fa = running at free air

cs = customer specs · cu = customer unit

Subject to alterations

3.3 Data according to ErP directive

Installation category

A

Efficiency category

Static

Variable speed drive

Yes

Specific ratio

*

1.00

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

40.2

38.5

42.5

Efficiency grade N

59.7

58

62

Power input P

ed

/ kW

0.14

Air flow q

v

/ m³/h

455

Pressure increase total p

sf

/ Pa

418

Speed n / min

-1

3840

Data established at point of optimum efficiency

3.4 Technical features

Mass

1.8 kg

Size

190 mm

Surface of rotor

Galvanised

Material of impeller

Plastic PA66, fibreglass-reinforced

Number of blades

7

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP 44; Depending on installation and
position

Insulation class

"B"

Humidity class

F3-1

Mounting position

Any

Condensate discharge
holes

None

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Motor current limit
- Soft start
- Control input 0-10 VDC / PWM
- Over-temperature protected
electronics / motor

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Motor protection

Thermal overload protector (TOP) wired
internally

Cable exit

Variable

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 60335-1; CE

Approval

UL 507; CSA C22.2 Nr.113

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

For depth of screw, see chapter 3.1 Product drawing

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

;

Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+ 80 °C

Min. permissible
ambient motor temp.
(transp./storage)

- 40 °C

3.7 Electromagnetic compatibility

EMC interference
immunity

Acc. to EN 61000-6-2

EMC harmonics

Acc. to EN 61000-3-2/3

EMC interference
emission

Acc. to EN 61000-6-3 (household
environment)

Item no. 51069-5-9970 · Revision 72864 · Release 2011-02-18 · Page 5 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for R3G190-AF50-01

Page 1: ...sonnel are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the d...

Page 2: ...ire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Befo...

Page 3: ...the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving highl...

Page 4: ...blue 1 3 PE green yellow 2 1 Tach output white 2 2 GND blue 2 3 10V red 2 4 0 10V yellow 3 Depth of screw min 8 mm max 10 mm 4 Pilot hole prepared for self tapping screw M4 depth of screw max 6 mm 5...

Page 5: ...chnical features Motor current limit Soft start Control input 0 10 VDC PWM Over temperature protected electronics motor Touch current acc IEC 60990 measuring network Fig 4 TN system 3 5 mA Motor prote...

Page 6: ...ssible Maintain a distance to the power supply line when routing the control lines of the device Ensure a sufficiently large clearance Recommendation clearance 10 cm separate cable routing NOTE Water...

Page 7: ...8 0 10 V PWM yellow Control input 0 10 V or PWM electrically isolated 9 Tach white Tach output open collector 1 pulse per revolution electrically isolated 11 10V max 1 1 mA red Voltage output 10 V ma...

Page 8: ...on Switch on the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching off the device for maintenance work Switch on the device via the con...