4.4 Connection diagram
Drawing preliminary!
Not switchable via power supply. Restart via input voltage only after 5 minute delay.
No.
Conn.
Designation
Color
Function/assignment
4
L
black
Supply connection, power supply, phase, voltage range see nameplate, 50/60 Hz
3
N
blue
Supply connection, power supply, neutral conductor, voltage range see nameplate, 50/60 Hz
1
PE
green/
yellow
Ground connection
8
0-10 V / PWM
yellow
0-10 V / PWM control input, Ri=100 kΩ, SELV
9
Tacho
white
Tach output, open collector, 1 pulse per revolution, Isink max = 10 mA, SELV
11
+10 V
red
Fixed voltage output 10 VDC +/-3 %, Imax.= 1.1 mA, short-circuit-proof, power supply for ext.
devices (e.g. potentiometers), SELV
12
GND
blue
Reference ground for control interface, SELV