Operating instructions
R2E225-AT55-12
Translation of the original operating instructions
3.2 Nominal data
Motor
M2E068-DF
Phase
1~
1~
1~
Nominal voltage / VAC
115
115
115
Frequency / Hz
50
60
60
Type of data definition
fa
fa
fa
Valid for approval /
standard
CE
CE
UL 2111
Speed / min
-1
2500
2600
2600
Power input / W
85
120
125
Current draw / A
0.75
1.05
1.05
Motor capacitor / µF
8
8
8
Capacitor voltage / VDB
220
220
220
Min. back pressure / Pa
0
0
0
Max. ambient
temperature / °C
60
55
55
ml = max. load · me = max. efficiency · fa = running at free air
cs = customer specs · cu = customer unit
Subject to alterations
3.3 Technical features
Mass
2.3 kg
Size
225 mm
Surface of rotor
Uncoated
Material of impeller
Plastic PA6, fibreglass-reinforced
Number of blades
11
Direction of rotation
Clockwise, seen on rotor
Type of protection
IP 44; Depending on installation and
position
Insulation class
"B"
Humidity class
F0
Mounting position
Any
Condensate discharge
holes
None
Operation mode
S1
Motor bearing
Ball bearing
Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)
< 0.75 mA
Motor protection
Thermal overload protector (TOP) wired
internally
Cable exit
Axial
Protection class
I (if protective earth is connected by
customer)
Product conforming
to standard
EN 60335-1; CE
Approval
UL 2111; CSA C22.2 Nr.77
For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.
3.4 Mounting data
For depth of screw, see chapter 3.1 Product drawing
;
Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).
Strength class for
mounting screws
8.8
You can obtain additional mounting data from the product drawing if
necessary.
3.5 Transport and storage conditions
;
Use the device in accordance with its protection type.
Max. permissible
ambient motor temp.
(transp./ storage)
+ 80 °C
Min. permissible
ambient motor temp.
(transp./storage)
- 40 °C
Item no. 11315-5-9970 · Revision 73098 · Release 2011-01-21 · Page 5 / 9