background image

Operating instructions

M4Q045-BD03-04

Translation of the original operating instructions

5.2 Safety inspection

What to check

How to check

How often

What action?

Device for
damage

Visual inspection At least every

6 months

Replace device

Fastening the
cables

Visual inspection At least every

6 months

Fasten

Fastening the
protective earth
terminal

Visual inspection At least every

6 months

Fasten

Insulation of
cables for
damage

Visual inspection At least every

6 months

Replace cables

Abnormal
bearing noise

acoustic

At least every
6 months

Replace device

5.3 Disposal

For ebm-papst, environmental protection and resource preservation are
top priority corporate goals.
ebm-papst operates an environmental management system which is
certified in accordance with ISO 14001 and rigorously implemented
around the world on the basis of German standards.
Right from the development stage, ecological design, technical safety
and health protection are fixed criteria.
The following section contains recommendations for ecological disposal
of the product and its components.

5.3.1 Country-specific legal requirements

NOTE
Country-specific legal requirements

Always observe the applicable country-specific legal
regulations with regard to the disposal of products or waste
occurring in the various phases of the life cycle. The
corresponding disposal standards are also to be heeded.

5.3.2 Disassembly

Disassembly of the product must be performed or supervised by
qualified personnel with the appropriate technical knowledge.
The product is to be disassembled into suitable components for disposal
employing standard procedures for motors.

WARNING
Heavy parts of the product may drop off. Some of the
product components are heavy. These components
could drop off during disassembly.

This can result in fatal or serious injury and material damage.
→ Secure components before unfastening to stop them falling.

5.3.3 Component disposal

The products are mostly made of steel, copper, aluminum and plastic.
Metallic materials are generally considered to be fully recyclable.
Separate the components for recycling into the following categories:

Steel and iron

Aluminum

Non-ferrous metal, e.g. motor windings

Plastics, particularly with brominated flame retardants, in accordance
with marking

Insulating materials

Cables and wires

Electronic scrap, e.g. circuit boards

Only ferrite magnets and not rare earth magnets are used in external
rotor motors from ebm-papst Mulfingen GmbH & Co. KG.

;

Ferrite magnets can be disposed of in the same way as normal iron
and steel.

Electrical insulating materials on the product, in cables and wires are
made of similar materials and are therefore to be treated in the same
manner.
The materials concerned are as follows:

Miscellaneous insulators used in the terminal box

Power cables

Cables for internal wiring

Electrolytic capacitors

Dispose of electronic components employing the proper procedures for
electronic scrap.

→ Please contact ebm-papst for any other questions on disposal.

Item no. 11483-5-9970 · ENU · Change 252384 · Approved 2022-06-08 · Page 9 / 9

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for M4Q045-BD03-04

Page 1: ...d maintained and otherwise used by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work...

Page 2: ...ny loose fitting or dangling clothing or jewelry while working on rotating parts Protect long hair with a cap WARNING Ejected parts If the motor is operated with attached fan blades missing protective...

Page 3: ...with severe vibration oscillation This also includes vibration transmitted to the motor from the customer installation Operation in medical equipment with a life sustaining or life support function Co...

Page 4: ...housing or guard grille 2 3 Nm 3 Tightening torque for screw to fasten fan impeller 1 4 Nm 4 Tightening torque for nuts to fasten mounting bracket 2 3 Nm 5 Direction of rotation counterclockwise view...

Page 5: ...E UKCA Approval CSA C22 2 No 77 EAC UL 1004 2 Use the device in accordance with its degree of protection Information on surface quality The surfaces of the products conform to the generally applicable...

Page 6: ...for the current level indicated on the nameplate For determining the cross section note the sizing criteria according to EN 61800 5 1 The protective earth must have a cross section equal to or greater...

Page 7: ...instructions 4 4 Connection diagram L blue PE green yellow N brown Item no 11483 5 9970 ENU Change 252384 Approved 2022 06 08 Page 7 9 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phon...

Page 8: ...ing the device CAUTION The motor restarts automatically when operating voltage is applied e g after a power failure Risk of injury Keep out of the motor s danger zone When working on the motor switch...

Page 9: ...chnical knowledge The product is to be disassembled into suitable components for disposal employing standard procedures for motors WARNING Heavy parts of the product may drop off Some of the product c...

Reviews: