4.5 Connection diagram

No.

Conn.

Designation

Function/assignment

KL 1

1

L1

Supply connection, power supply 3-phase 380-480 VAC, 50/60 Hz

KL 1

2

L2

Supply connection, power supply 3-phase 380-480 VAC, 50/60 Hz

KL 1

3

L3

Supply connection, power supply 3-phase 380-480 VAC, 50/60 Hz

PE

PE

Ground connection, PE connection

KL 2

1

NO

Status relay, floating status contact, make for failure

KL2

2

COM

Status relay, floating status contact; changeover contact; common connection; contact rating 250 VAC / max.
2 A (AC1) / min. 10 mA

KL2

3

NC

Status relay, floating status contact, break for failure

KL 3

1

RSA

Bus connection RS485, RSA, MODBUS RTU

KL 3

2

RSB

Bus connection RS485, RSB, MODBUS RTU

KL 3

3 / 10

GND

Reference ground for control interface

KL 3

4

Ain1 U

Analog input 1 (set value), 0-10 V, Ri = 100 kΩ, adjustable curves, only usable as alternative to input Ain1I

KL 3

5

+ 10 V

Fixed voltage output 10 VDC, +10 V ±3%; max. 10 mA; short-circuit-proof; power supply for external
devices (e.g. pot)

KL 3

6

Ain1 I

Analog input 1 (set value), 4-20 mA, Ri = 100 Ω, adjustable curves, only usable as alternative to input Ain1U

KL 3

7

Din1

Digital input 1: enable electronics, enable: pin open or applied voltage 5...50 VDC: disable: bridge to GND or
applied voltage < 1 VDC; reset function: triggers software reset after a level change to < 1 V

KL 3

8

Din2

Digital input 2: Switching parameter sets 1/2; according to EEPROM setting, the valid or used parameter set
can be selected via bus or via digital input DIN2. Parameter set 1: pin open or applied voltage 5-50 VDC;
parameter set 2: bridge to GND or applied voltage < 1 VDC

KL 3

9

Din3

Digital input 3: according to EEPROM setting, the integrated controller's direction of action can be selected as
normal/inverse via bus or digital input; normal: pin open or applied voltage 5-50 VDC inverse: bridge to GND
or applied voltage < 1 VDC

KL 3

11

Ain2 U

Analog input 2, measured value 0-10 V, Ri = 100 kΩ, adjustable curve, only usable as alternative to input Ain2I

KL 3

12

+ 20 V

Fixed voltage output 20 VDC, 20 V +25/-10%, max. 50 mA, short-circuit-proof power supply for external
devices (e.g. sensors)

KL 3

13

Ain2 I

Analog input 2, measured value: 4-20 mA, Ri = 100 Ω, adjustable curve, only usable as alternative to input
Ain2U

KL 3

14

Aout

Analog output 0-10 V, max. 5 mA, output of current motor modulation level / of the current motor speed.
Adjustable curve.

Item no. 55789-5-9970 · ENU · Change 260717 · Approved 2022-06-23 · Page 9 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K3G710-PW06-01

Page 1: ...e permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the devi...

Page 2: ...evice against accidental contact Before working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or brok...

Page 3: ...forming all maintenance work Conveying air at an ambient air pressure between 800 mbar and 1050 mbar Using the device within the permitted ambient temperature range see Chapter 3 6 Transport and stora...

Page 4: ...ghtening torque 6 0 9 Nm 5 Tightening torque 3 5 0 5 Nm 6 Attachment holes for FlowGrid 50710 2 2957 not included in scope of delivery 7 Motor support plate Installation position shaft horizontal moto...

Page 5: ...ts validity the conformity must be confirmed again The product does not fall within the scope of Regulation EU 2019 1781 due to the exception specified in Article 2 2a motors completely integrated int...

Page 6: ...cessary after consultation with the network operator that this device is only connected to a connection point with an Ssc value greater than or equal to 250 times the rated output of the arrangement 4...

Page 7: ...to wires or cables Water ingress at the customer end of the cable can damage the device Make sure the end of the cable is connected in a dry environment Only connect the device to circuits that can be...

Page 8: ...here is no strain on the connections For tightening torques see Chapter 3 1 Product drawing NOTE Tightness and strain relief are dependent on the cable used This must be checked by the user 4 3 2 Conn...

Page 9: ...cs enable pin open or applied voltage 5 50 VDC disable bridge to GND or applied voltage 1 VDC reset function triggers software reset after a level change to 1 V KL 3 8 Din2 Digital input 2 Switching p...

Page 10: ...ng Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessively high vibration levels can lead to premature failure The maximum per...

Page 11: ...e from supply and remove mechanical blockage Line voltage faulty Check line voltage restore power supply Attention The error message resets automatically Device restarts automatically without warning...

Page 12: ...aintenance intervals to the actual level of dust exposure 6 3 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testing volta...

Page 13: ...tallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plasti...

Reviews: