Operating instructions

K3G710-AP02-01

Translation of the original operating instructions

No.

Conn.

Designation

Function / assignment

KL 3

6

Ain1 I

Analogue input 1, set value: 4-20 mA; Ri = 100 Ω, parametrisable curve, only usable as alternative to input
Ain1 U; SELV

KL 3

7

Din1

Digital input 1: enabling of electronics,
enabling: open pin or applied voltage 5-50 VDC
disabling: bridge to GND or applied voltage <1 VDC
reset function: triggers software reset after a level change to <1 VDC; SELV

KL 3

8

Din2

Digital input 2: parameter set switch 1/2, according to EEPROM setting, the valid/used parameter set can be
selected via bus or via digital input DIN2.
Parameter set 1: open pin or applied voltage 5-50 VDC
Parameter set 2: bridge to GND or applied voltage <1 VDC; SELV

KL 3

9

Din3

Digital input 3: controller function of integrated controller, according to EEPROM setting, the controller function of
the integrated controller is normally/inversely selectable per bus or per digital input Din 3
normal: open pin or applied voltage 5-50 VDC
inverse: bridge to GND or applied voltage <1 VDC; SELV

KL 3

11

Ain2 U

Analogue input 2, actual value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only usable as alternative to input
Ain2; SELV

KL 3

12

+ 20 V

Fixed voltage output 20 VDC; +20 V +25/-10%, max. 50 mA; short-circuit-proof; supply voltage for external
devices (e.g. sensors); SELV
Alternatively: +24 VDC input for parametrization without mains power

KL 3

13

Ain2 I

Analogue input 2, actual value: 4-20 mA, Ri = 100 Ω, parametrisable curve, only usable as alternative to input
Ain2 U; SELV

KL 3

14

Aout

Analogue output 0-10 VDC, max. 5 mA, output of the current motor level control coefficient / motor speed
parametrisable curve; SELV

Item no. 53570-5-9970 · ENG · Revision 209539 · Release 2021-01-29 · Page 11 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K3G710-AP02-01

Page 1: ...ry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is install...

Page 2: ...Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill DANGER Flying parts Missing safety devices may cause balancing weights...

Page 3: ...r 3 2 Nominal data Operating the device with all protective features in place Minding the operating instructions Improper use Using the device in the following ways is particularly prohibited and may...

Page 4: ...m 1 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 2 Tightening torque 3 5 0 5 Nm 3 Inlet nozzle with pressure tap k factor 545 Item no 53570 5 9970 ENG Revision 209539 Release 2021 01 2...

Page 5: ...ination in a standardised measurement configuration 3 4 Technical features Mass 93 kg Size 710 mm Motor size 150 Surface of rotor Coated in black Material of electronics housing Die cast aluminium Mat...

Page 6: ...ion engineer or operator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected to a connection point with a Ssc value that is great...

Page 7: ...nto leads or wires Water enters at the cable end on the customers side and can damage the device Make sure that the cable end is connected in a dry environment Connect the device only to circuits that...

Page 8: ...protection Due to the locked rotor protection the start up current LRA is equal to or less than the nominal current FLA 4 3 Connection in terminal box 4 3 1 Preparing connection lines for the connect...

Page 9: ...xample When routing the cable ensure that the screwed cable glands are arranged at the bottom The cables must always be routed downwards Fig 4 Cable routing for fans installed upright 4 4 Factory sett...

Page 10: ...ontact common connection contact rating 250 VAC max 2 A AC1 min 10 mA KL2 3 NC Status relay floating status contact break for failure KL 3 1 RSA Bus connection RS 485 RSA MODBUS RTU SELV KL 3 2 RSB Bu...

Page 11: ...OM setting the controller function of the integrated controller is normally inversely selectable per bus or per digital input Din 3 normal open pin or applied voltage 5 50 VDC inverse bridge to GND or...

Page 12: ...nce frequencies that may be present When regulating the speed pass through resonance ranges as quickly as possible or find another remedy Operation at excessive vibration levels can lead to premature...

Page 13: ...f de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The error message resets automatically The device starts up again aut...

Page 14: ...with maintenance free ball bearings The lifetime lubrication of the ball bearings is designed for a service life of 40 000 hours Please contact ebm papst if bearing replacement is required after this...

Page 15: ...ts could drop off during disassembly This can result in fatal or serious injury and material damage Secure components before unfastening to stop them falling 6 4 3 Component disposal The products are...