ebm-papst K3G500-RL96-01 Operating Instructions Manual Download Page 9

Operating instructions

K3G500-RL96-01

Translation of the original operating instructions

4.5 Connection diagram

Drawing preliminary!

No.

Conn.

Designation

Color

Function/assignment

1

1, 2

PE

green/
yellow

Protective earth

1

3

L1

black

Power supply

1

4

L2

black

Power supply

1

5

L3

black

Power supply

1

6

NC

white 1

Status relay, floating status contact, break for failure,
contact rating 250 VAC / 2 A (AC1) / min. 10 mA; reinforced insulation on supply side and basic
insulation on control interface side

1

7

COM

white 2

Status relay, floating status contact, break for failure,
contact rating 250 VAC / 2 A (AC1) / min. 10 mA; reinforced insulation on supply side and basic
insulation on control interface side

2

8

0-10V

yellow

Analog input (set value), 0-10 V, Ri = 100 kΩ, adjustable curve, SELV

2

10

RSB

brown

RS485 interface for MODBUS, RSB; SELV

2

11

RSA

white

RS485 interface for MODBUS, RSA; SELV

2

12

GND

blue

Reference ground for control interface, SELV

2

13

+10V

red

Fixed voltage output 10 VDC, +10 V ±3%, max. 10 mA, short-circuit-proof power supply for
external devices (e.g. pot), SELV
fixed voltage input 24 VDC for setting parameters via MODBUS without line voltage supply

Item no. 52548-5-9970 · ENU · Change 212422 · Approved 2020-07-14 · Page 9 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K3G500-RL96-01

Page 1: ...are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the de...

Page 2: ...ore working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and caus...

Page 3: ...2 Nominal data Operating the device with all protective devices Following the operating instructions Improper use In particular operating the device in the following ways is prohibited and could be h...

Page 4: ...install support struts only vertically as illustrated or rotor on bottom rotor on top on request 2 Cable PVC AWG18 6x crimped ferrules 3 Cable PVC AWG22 5x crimped ferrules Item no 52548 5 9970 ENU C...

Page 5: ...a standardized measurement setup 3 4 Technical description Weight 24 62 kg Size 500 mm Motor size 112 Rotor surface Painted black Electronics housing material Die cast aluminum Impeller material PP pl...

Page 6: ...rated output of the arrangement It is the responsibility of the installation engineer or operator owner of the device to ensure if necessary after consultation with the network operator that this devi...

Page 7: ...necessary to connect an additional protective earth conductor by way of the extra protective earth terminal provided on the device The protective earth terminal is located on the housing and provided...

Page 8: ...ade for the device by ebm papst Mode parameter set 1 PWM control Mode parameter set 2 PWM control Fan device address 01 Max PWM 100 Min PWM 5 Save set value to EEPROM Yes Set value requirement Analog...

Page 9: ...g 250 VAC 2 A AC1 min 10 mA reinforced insulation on supply side and basic insulation on control interface side 2 8 0 10V yellow Analog input set value 0 10 V Ri 100 k adjustable curve SELV 2 10 RSB b...

Page 10: ...issible vibration severity must not exceed 3 5 mm s and should be checked at intervals of 6 months It is to be determined at the motor mount at the motor support plate at least in axial direction and...

Page 11: ...eck line voltage restore power supply Attention The error message resets automatically Device restarts automatically without warning Faulty connection Isolate from supply correct connection see connec...

Page 12: ...after that period contact ebm papst Adapt the maintenance intervals to the actual level of dust exposure 6 3 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tr...

Page 13: ...tallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plasti...

Reviews: