Operating instructions
K3G500-PB33-05
Translation of the original operating instructions
4.5 Connection screen
No.
Conn.
Designation
Function / assignment
KL 1
1
L1
Mains connection, power supply, phase, see type plate for voltage range
KL 1
2
L2
Mains connection, power supply, phase, see type plate for voltage range
KL 1
3
L3
Mains connection, power supply, phase, see type plate for voltage range
PE
PE
Earth connection, PE connection
KL 2
1
NO
Status relay, floating status contact, make for failure
KL 2
2
COM
Status relay, floating status contact, changeover contact, common connection, contact rating, max. 250 VAC/2
A (AC1)/min. 10 mA
KL 2
3
NC
Status relay, floating status contact, break for failure
KL 3
1
RSA
Bus connection RS485, RSA, MODBUS RTU; SELV
KL 3
2
RSB
Bus connection RS485, RSB, MODBUS RTU; SELV
KL 3
3 / 10
GND
Signal ground for control interface, SELV
KL 3
4
Ain1 U
Analogue input 1, set value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only for use as alternative to input
Ain1; SELV
KL 3
5
+ 10 V
Fixed voltage output 10 VDC, +10 V +/-3 %, max. 10 mA, short-circuit-proof, power supply for ext. devices
(e.g. potentiometer); SELV