ebm-papst K3G500-PA26-C1 Instruction Manual Download Page 9

Operating instructions

K3G500-PA26-C1

Translation of the original operating instructions

4.5 Connection diagram

Drawing preliminary!

No.

Conn.

Designation

Function/assignment

KL 1

1

L1

Supply connection, power supply; for nominal voltage range see technical data

KL 1

2

L2

Supply connection, power supply; for nominal voltage range see technical data

KL 1

3

L3

Supply connection, power supply; for nominal voltage range see technical data

PE

PE

PE

Ground connection, PE connection

KL 2

1

NO

Status relay, floating status contact, make for failure

KL2

2

COM

Status relay, floating status contact, common connection, contact rating 250 VAC / 2 A (AC1) / min. 10 mA,
reinforced insulation on supply side and on control interface side

KL2

3

NC

Status relay, floating status contact, break for failure

KL 3

1

RSA

Bus connection RS485, RSA, MODBUS-RTU; SELV

KL 3

2

RSB

Bus connection RS485, RSB, MODBUS-RTU; SELV

KL 3

3 / 10

GND

Reference ground for control interface; SELV

KL 3

4

Ain1 U

Analog input 1, set value: 0-10 V, Ri = 100 kΩ, adjustable curve, only usable as alternative to input Ain1 I;
SELV

KL 3

5

+ 10 V

Fixed voltage output 10 VDC, + 10 V +/-3%, max. 10 mA, short-circuit-proof, power supply for ext. devices
(e.g. potentiometers); SELV

Item no. 55936-5-9970 · ENU · Change 209539 · Approved 2021-02-12 · Page 9 / 14

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K3G500-PA26-C1

Page 1: ...e permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the devi...

Page 2: ...ore working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and caus...

Page 3: ...Chapter 3 2 Nominal data Operating the device with all protective devices Following the operating instructions Improper use In particular operating the device in the following ways is prohibited and c...

Page 4: ...tor on top on request 2 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Cable diameter min 9 mm max 16 mm tightening torque 6 0 9 Nm 4 Tightening torque 3 5 0 5 Nm 5 Inlet ring with pre...

Page 5: ...is determined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 41 8 kg Size 500 mm Motor size 150 Rotor surface Painted black Electronics housing...

Page 6: ...n point with an Ssc value greater than or equal to 33 times the rated output of the arrangement 4 CONNECTION AND STARTUP 4 1 Mechanical connection CAUTION Risk of cutting and crushing when removing de...

Page 7: ...ustomer end of the cable can damage the device Make sure the end of the cable is connected in a dry environment Only connect the device to circuits that can be switched off with an all pole disconnect...

Page 8: ...ons For tightening torques see Chapter 3 1 Product drawing NOTE Tightness and strain relief are dependent on the cable used This must be checked by the user 4 3 2 Connecting wires to terminals WARNING...

Page 9: ...on contact rating 250 VAC 2 A AC1 min 10 mA reinforced insulation on supply side and on control interface side KL2 3 NC Status relay floating status contact break for failure KL 3 1 RSA Bus connection...

Page 10: ...PROM setting the integrated controller s direction of action can be selected via bus or digital input Din3 normal pin open or applied voltage 5 50 VDC inverse bridge to GND or applied voltage 1 VDC SE...

Page 11: ...ng Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessively high vibration levels can lead to premature failure The maximum per...

Page 12: ...e from supply and remove mechanical blockage Line voltage faulty Check line voltage restore power supply Attention The error message resets automatically Device restarts automatically without warning...

Page 13: ...aintenance intervals to the actual level of dust exposure 6 3 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testing volta...

Page 14: ...tallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plasti...

Reviews: