ebm-papst K3G500-AP25-01 Operating Instructions Manual Download Page 5

Operating instructions

K3G500-AP25-01

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G150-FF

Phase

3~

Nominal voltage / VAC

400

Nominal voltage
range / VAC

380 .. 480

Frequency / Hz

50/60

Method of obtaining
data

ml

Speed (rpm) / min

-1

1780

Power consumption / W

2825

Current draw / A

4.3

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

60

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to Commission Regulation (EU) 327/
2011

Actual

Req. 2015

01 Overall efficiency η

es

/ %

66.7

56.3

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

72.4

62

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart ·
HRA 590344
D-74673 Mulfingen

08 Type

K3G500-AP25-01

09 Power consumption P

ed

/ kW

2.86

09 Air flow q

v

/ m³/h

8140

09 Pressure increase total p

sf

/

Pa

799

10 Speed (rpm) n / min

-1

1790

11 Specific ratio

*

1.01

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller

combination in a standardized measurement setup.

3.4 Technical description

Weight

40 kg

Size

500 mm

Motor size

150

Rotor surface

Painted black

Electronics housing
material

Die-cast aluminum

Impeller material

Sheet aluminum

Support plate material

Sheet steel, galvanized

Support bracket
material

Steel, coated with black plastic

Inlet nozzle material

Sheet steel, galvanized

Number of blades

7

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP55

Insulation class

"F"

Moisture (F) /
Environmental (H)
protection class

H1

Installation position

See product drawing

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Output for slave 0-10 V
- Input for sensor 0-10 V or 4-20 mA
- External 24 V input (parameter setting)
- External release input
- Alarm relay
- Integrated PID controller
- Power limiter
- Motor current limitation
- PFC, passive
- RS-485 MODBUS-RTU
- Soft start
- EEPROM write cycles: 100,000
maximum
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Thermal overload protection for
electronics/motor
- Line undervoltage / phase failure
detection

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Electrical hookup

Terminal box

Motor protection

Reverse polarity and locked-rotor
protection

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 61800-5-1; CE

Approval

CSA C22.2 No. 77 + CAN/CSA-
E60730-1; EAC; UL 1004-7 + 60730-1

Item no. 50651-5-9970 · ENU · Change 209539 · Approved 2021-02-12 · Page 5 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K3G500-AP25-01

Page 1: ...permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the devic...

Page 2: ...ore working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and caus...

Page 3: ...Chapter 3 2 Nominal data Operating the device with all protective devices Following the operating instructions Improper use In particular operating the device in the following ways is prohibited and c...

Page 4: ...rtically as illustrated or rotor on bottom rotor on top on request 2 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Inlet ring with pressure tap k factor 281 4 Tightening torque 3 5 0...

Page 5: ...otor impeller combination in a standardized measurement setup 3 4 Technical description Weight 40 kg Size 500 mm Motor size 150 Rotor surface Painted black Electronics housing material Die cast alumin...

Page 6: ...n with the network operator that this device is only connected to a connection point with a Ssc value that is greater than or equal to 120 times the rated output of the arrangement 4 CONNECTION AND ST...

Page 7: ...ustomer end of the cable can damage the device Make sure the end of the cable is connected in a dry environment Only connect the device to circuits that can be switched off with an all pole disconnect...

Page 8: ...multiple of the nominal value 4 2 6 Locked rotor protection Due to the locked rotor protection the starting current LRA is equal to or less than the nominal current FLA 4 3 Connection in terminal box...

Page 9: ...ble a drip edge can be produced by fitting a cable tie directly in front of the cable gland for example 4 4 Factory settings Factory settings made for the device by ebm papst Mode parameter set 1 PWM...

Page 10: ...contact changeover contact common connection contact rating 250 VAC max 2 A AC1 min 10 mA KL2 3 NC Status relay floating status contact break for failure KL 3 1 RSA Bus connection RS485 RSA MODBUS RTU...

Page 11: ...EEPROM setting the integrated controller s direction of action can be selected via bus or digital input Din3 normal pin open or applied voltage 5 50 VDC inverse bridge to GND or applied voltage 1 VDC...

Page 12: ...ng Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessively high vibration levels can lead to premature failure The maximum per...

Page 13: ...e from supply and remove mechanical blockage Line voltage faulty Check line voltage restore power supply Attention The error message resets automatically Device restarts automatically without warning...

Page 14: ...aintenance intervals to the actual level of dust exposure 6 3 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testing volta...

Page 15: ...tallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plasti...

Reviews: