Impeller running
roughly

Imbalance in rotating
parts

Clean the device; if
imbalance is still
evident after cleaning,
replace the device.
If you have
attached any weight
clips during cleaning,
make sure to remove
them afterwards.

Motor does not turn

Mechanical blockage

Switch off, de-
energise, and
remove mechanical
blockage.

Mains supply voltage
faulty

Check mains supply
voltage,
restore power
supply.
Important! The error
message resets
automatically.
The device starts up
again automatically
without advance
warning.

Faulty connection

De-energise, correct
connection, see
connection diagram.

Motor winding broken Replace device
Insufficient cooling

Improve cooling. Let
the device cool down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.
Alternatively, reset
the error message by
applying a control
signal of <0.5 V to
DIN1 or by short
circuiting Din1 to
GND.

Ambient temperature
too high

Reduce the ambient
temperature. Let the
device cool down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.
Alternatively, reset
the error message by
applying a control
signal of <0.5 V to
DIN1 or by short
circuiting Din1 to
GND.

Unacceptable
operating point (e.g.
counterpressure is
too high)

Correct the operating
point. Let the device
cool down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.
Alternatively, reset
the error message by
applying a control
signal of <0.5 V to
DIN1 or by short
circuiting Din1 to
GND.

If you have any other problems, contact ebm-papst.

6.1 Vibration test

Checking the fan for mechanical vibrations based on ISO 14694.
Recommendation: every 6 months. Maximum vibration severity is 3.5
mm/s measured at the motor’s fastening diameter on the motor support
plate towards and perpendicular to the motor’s axis of rotation.

Fig. 3: Example showing vibration measurement. Positioning of the
sensors will vary depending on the device and the circumstances of
installation.

6.2 Cleaning

NOTE
Damage to the device during cleaning

Malfunction possible
→ Do not use a high-pressure cleaner to clean the device.# Do

not use any acid, alkali or solvent-based cleaning agents.

→ Do not use any pointed or sharp-edged objects for cleaning

Item no. 55251-5-9970 · ENG · Revision 91062 · Release 2016-10-05 · Page 11 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K3G400-PA29-19

Page 1: ...ted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be...

Page 2: ...ve come to a standstill DANGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing bodily harm Take appropriate safety measures WA...

Page 3: ...ice in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations Th...

Page 4: ...wn in the illustration or rotor on bottom rotor on top on request 2 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Tightening torque 3 5 0 5 Nm 4 Inlet nozzle with pressure tap k facto...

Page 5: ...d from the mains Over temperature protected electronics motor Line undervoltage phase failure detection Touch current acc IEC 60990 measuring network Fig 4 TN system 3 5 mA Electrical leads Via termin...

Page 6: ...ere is a risk of damage to the impeller Check the device for transport damage Damaged devices must no longer be installed Install the undamaged device according to your application CAUTION Possibility...

Page 7: ...idual current operated device If the use of a residual current device RCD is required in your installation only universal residual current devices type B or B are permissible Residual current devices...

Page 8: ...y ebm papst Control mode parameter set 1 PWM controlling Control mode parameter set 2 PWM controlling Fan device adress 1 Max PWM 100 Min PWM 5 Save set value to EEPROM Yes Set value control Analogue...

Page 9: ...n pin or applied voltage 5 50 VDC disabling bridge to GND or applied voltage 1 VDC reset function triggers software reset after a level change to 1 VDC SELV KL 3 8 Din2 Digital input 2 parameter set s...

Page 10: ...off the device Switching off the device during operation Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching off the devic...

Page 11: ...rnatively reset the error message by applying a control signal of 0 5 V to DIN1 or by short circuiting Din1 to GND Unacceptable operating point e g counterpressure is too high Correct the operating po...

Page 12: ...gical disposal of the product and its components 6 4 1 Country specific legal requirements NOTE Country specific legal requirements Always observe the applicable country specific legal regulations wit...

Reviews: