Operating instructions

K3G400-HB41-01

Translation of the original operating instructions

Approval

UL 1004-7 + 60730-1; EAC; CSA
C22.2 No. 77 + CAN/CSA-E60730-1

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. The product is to be protected against UV radiation to
prevent the formation of patches and fading. Changes in color are not a
reason for complaint and are not covered by the warranty. UV radiation
in the frequency range and the intensity of natural solar radiation has no
effect on the technical properties of the products.

3.5 Mounting data

Further mounting data can be taken from the product drawing or Chapter
4.1 Mechanical connection as required.

Strength class of
screws

8.8

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

3.6 Transport and storage conditions

Max. permitted
ambient temp. for
motor (transport/
storage)

+80 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

-40 °C

3.7 Electromagnetic compatibility

EMC immunity to
interference

According to EN 61000-6-2 (industrial
environment)

EMC interference
emission

According to EN 61000-6-4 (industrial
environment)

If several devices are switched in parallel on the supply side
so that the line current of the arrangement is in the range of 16-
75 A, then this arrangement conforms to IEC 61000-3-12
provided that the short-circuit power S

sc

at the connection point

of the customer system to the public power system is greater
than or equal to 120 times the rated output of the arrangement.
It is the responsibility of the installation engineer or operator/
owner of the device to ensure, if necessary after consultation
with the network operator, that this device is only connected to
a connection point with a S

sc

value that is greater than or equal

to 120 times the rated output of the arrangement.

4. CONNECTION AND STARTUP

4.1 Mechanical connection

CAUTION
Risk of cutting and crushing when removing device
from packaging

→ Carefully remove the device from the packaging by grasping

hold of the frame. Never subject to any impact.

→ Wear safety shoes and cut-resistant safety gloves.

CAUTION
Device weighs over 25 kg! Heavy load when unpacking
device.

Risk of physical injury, such as back injuries.
→ Use suitable hoisting equipment to remove the device from

its packaging.

NOTE
Damage to the device from vibration

Bearing damage, shorter service life
→ The fan must not be subjected to force or excessive vibration

from sections of the installation.

→ If the fan is connected to air ducts, the connection should

be isolated from vibration, e.g. using compensators or similar
elements.

→ Ensure stress-free attachment of the fan to the

substructure.

;

The fan may not be handled in the area around the inlet nozzle during
transport and installation.
There is a risk of damage to the impeller.

;

Check the device for transport damage. Damaged devices are not to
be installed.

;

Install the undamaged device in accordance with your application.

4.1.1 Installation of RadiPac fan

Use is always to be made of appropriate hoisting equipment and a
suitable lifting device when transporting the fan for installation purposes.
Only suitable round slings are to be used for this purpose (see Chapter
3.4 Technical description for weight of product). Use four round slings
passed around the struts for lashing purposes. Position the round slings
as shown in the hoisting diagram below. Make sure that the struts of the
support bracket on the left and right of the motor are vertical. During
installation, only transport the fan in the installation position as shown in
the product drawing. Heed the information given on the device! During
transportation, an acceleration of 2 g must not be exceeded.

Item no. 56857-5-9970 · ENU · Change 260705 · Approved 2022-09-01 · Page 6 / 15

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K3G400-HB41-01

Page 1: ...d technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety r...

Page 2: ...have to be taken by the user NOTE Electrical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DAN...

Page 3: ...stationary systems Performing all maintenance work Conveying air at an ambient air pressure between 800 mbar and 1050 mbar Using the device within the permitted ambient temperature range see Chapter...

Page 4: ...r on top on request 2 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Cable diameter min 9 mm max 16 mm tightening torque 6 0 9 Nm 4 Tightening torque 3 5 0 5 Nm 5 Inlet ring with press...

Page 5: ...aluation loses its validity the conformity must be confirmed again The product does not fall within the scope of Regulation EU 2019 1781 due to the exception specified in Article 2 2a motors completel...

Page 6: ...er of the device to ensure if necessary after consultation with the network operator that this device is only connected to a connection point with a Ssc value that is greater than or equal to 120 time...

Page 7: ...ble can damage the device Make sure the end of the cable is connected in a dry environment Only connect the device to circuits that can be switched off with an all pole disconnection switch 4 2 1 Requ...

Page 8: ...multiple of the nominal value 4 2 6 Locked rotor protection Due to the locked rotor protection the starting current LRA is equal to or less than the nominal current FLA 4 3 Connection in terminal box...

Page 9: ...ible a drip edge can be produced by fitting a cable tie directly in front of the cable gland for example 4 4 Factory settings Factory settings made for the device by ebm papst Mode parameter set 1 PWM...

Page 10: ...on control interface side KL2 3 NC Status relay floating status contact option 1 break for failure option 2 break for error message for run monitor KL 3 1 RSA RS485 interface for MODBUS RSA SELV KL 3...

Page 11: ...SELV KL 3 10 Ain1 U Analog input 1 set value 0 10 V Ri 100 k adjustable curve SELV KL 3 11 Aout Analog output 0 10 VDC max 5 mA output of current motor modulation level motor speed adjustable curve S...

Page 12: ...ng Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with excessively high vibration levels can lead to premature failure The maximum per...

Page 13: ...e from supply and remove mechanical blockage Line voltage faulty Check line voltage restore power supply Attention The error message resets automatically Device restarts automatically without warning...

Page 14: ...aintenance intervals to the actual level of dust exposure 6 3 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors The tripping current is exceeded when AC testing volta...