ebm-papst K3G355-PJ75-05 Operating Instructions Manual Download Page 5

Operating instructions

K3G355-PJ75-05

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G112-EA

Phase

3~

Nominal voltage / VAC

400

Nominal voltage
range / VAC

380 .. 480

Frequency / Hz

50/60

Type of data definition

ml

Speed (rpm) / min

-1

2400

Power input / W

1100

Current draw / A

1.7

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

60

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data in accordance with ecodesign regulation EU 327/
2011

Actual

Request 2015

01 Overall efficiency η

es

/ %

69.2

51.9

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

79.3

62

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
rating plate on the product.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
County court Stuttgart · HRA 590344
D-74673 Mulfingen

08 Type

K3G355-PJ75-05

09 Power input P

ed

/ kW

1.09

09 Air flow q

v

/ m³/h

3655

09 Pressure increase total p

sf

/

Pa

692

10 Speed (rpm) n / min

-1

2405

11 Specific ratio

*

1.01

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data definition with optimum efficiency. The ErP data is determined using a motor-impeller

combination in a standardised measurement configuration.

3.4 Technical features

Mass

18 kg

Size

355 mm

Motor size

112

Surface of rotor

Coated in black

Material of terminal box

PP plastic

Material of electronics
housing

Die-cast aluminium

Material of impeller

Aluminium sheet

Material of mounting
plate

Sheet steel, galvanised

Material of support
bracket

Steel, galvanized

Number of blades

5

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP55

Insulation class

"F"

Humidity (F) /
environmental
protection class (H)

H1

Note ambient
temperature

Occasional start-up between -40°C and -
25°C is permissible.
For continuous operation at ambient
temperatures below -25°C (e.g.
refrigeration applications) we recommend
our fan version with special low-
temperature bearings.

Mounting position

Refer to product drawing

Condensation
drainage holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing; (sealed)

Technical features

- Output 10 VDC, max. 10 mA
- Operation and alarm display
- External 24 V input (programming)
- Alarm relay
- Integrated PID controller
- Motor current limit
- PFC, passive
- RS485 MODBUS RTU
- Soft start
-Maximum EEPROM write cycles
100,000
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Over-temperature protected
electronics / motor
- Line undervoltage / phase failure
detection

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical connection

Terminal box

Motor protection

Thermal overload protector (TOP) wired
internally

Protection class

I (if protective earth is connected by
customer)

Item no. 54828-5-9970 · ENG · Revision 202174 · Release 2018-12-20 · Page 5 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K3G355-PJ75-05

Page 1: ...rry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device The local industrial safety regulations must always be observed when working on the device Keep the workplace clean and tidy Untidiness in the working area increases the risk of ...

Page 2: ...e user NOTE Electrical or electromagnetic interferences after integrating the device in installations on the customer s side Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all parts ha...

Page 3: ...r at an ambient air pressure of 800 mbar to 1050 mbar Using the device in accordance with the permitted ambient temperature see chapter 3 6 Transport and storage conditions and chapter 3 2 Nominal data Operating the device with all protective features in place Minding the operating instructions Improper use Using the device in the following ways is particularly prohibited and may cause hazards Ope...

Page 4: ...e 1 8 0 3 Nm use the provided seal Cable diameter min 4 mm max 10 mm tightening torque 1 8 0 3 Nm 3 Cable diameter min 6 mm max 10 mm tightening torque 1 8 0 3 Nm use the provided seal Cable diameter min 4 mm max 7 mm tightening torque 1 8 0 3 Nm 4 Inlet nozzle with pressure tap k factor 148 5 Tightening torque 3 5 0 5 Nm 6 Mounting holes for FlowGrid Item no 54828 5 9970 ENG Revision 202174 Relea...

Page 5: ...on in a standardised measurement configuration 3 4 Technical features Mass 18 kg Size 355 mm Motor size 112 Surface of rotor Coated in black Material of terminal box PP plastic Material of electronics housing Die cast aluminium Material of impeller Aluminium sheet Material of mounting plate Sheet steel galvanised Material of support bracket Steel galvanized Number of blades 5 Direction of rotation...

Page 6: ...ut of the arrangement It is the responsibility of the installation engineer or operator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected to a connection point with a Ssc value that is greater than or equal to 250 times the rated output of the arrangement 4 CONNECTION AND START UP 4 1 Connecting the mechanical system CAUTION ...

Page 7: ...he installation situation it may be necessary to connect an additional protective earth conductor by way of the extra protective earth terminal provided on the device The protective earth terminal is located on the housing and provided with a protective earth symbol and a hole 4 2 2 Power supply connection fuse protection Assignment of conductor cross sections and the fuse protection required for ...

Page 8: ...ing the connection work ensure that no cables splice off Seal the terminal box 4 3 3 Cable routing No water may penetrate along the cable in the direction of the cable gland NOTE Damage caused by moisture penetration Moisture can penetrate into the terminal box if water is constantly present at the cable glands To prevent the constant accumulation of water at the cable glands the cable should be r...

Page 9: ...min 10 mA reinforced insulation on mains side and basic insulation on control interface side 8 GND Signal ground for control interface SELV 9 RSA RS 485 interface for MODBUS RSA SELV 10 RSB RS 485 interface for MODBUS RSB SELV 11 0 10 V Analogue input set value SELV 0 10 V Ri 100kΩ parametrisable curve 12 10 V Fixed voltage output 10 VDC SELV 10 V 3 max 10 mA short circuit proof power supply for e...

Page 10: ...s When putting the fan into service determine the speed ranges with excessive vibration levels and also any resonance frequencies that may be present When regulating the speed pass through resonance ranges as quickly as possible or find another remedy Operation at excessive vibration levels can lead to premature failure The maximum vibration severity may not exceed 3 5 mm s and should be checked e...

Page 11: ... remove them afterwards Motor does not turn Mechanical blockage Switch off de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The error message resets automatically The device starts up again automatically without advance warning Faulty connection De energise correct connection see connection diagram Motor winding broken...

Page 12: ...vice Tightness of screwed cable gland Visual inspection At least every 6 months Retighten replace if damaged Condensate discharge holes for clogging as necessary Visual inspection At least every 6 months Open bore holes Abnormal bearing noise acoustic At least every 6 months Replace device Vibration test Vibration tester acceleration or deceleration measurement Recommended every 6 months Clean imp...

Page 13: ... external rotor motors from ebm papst Mulfingen GmbH Co KG Ferrite magnets can be disposed of in the same way as normal iron and steel Electrical insulating materials on the product in cables and wires are made of similar materials and are therefore to be treated in the same manner The materials concerned are as follows Miscellaneous insulators used in the terminal box Power lines Cables for inter...

Reviews: