ebm-papst K3G310-PG93-21 Operating Instructions Manual Download Page 9

Operating instructions

K3G310-PG93-21

Translation of the original operating instructions

4.5 Connection diagram

Drawing preliminary!

No.

Conn.

Designation

Function/assignment

KL1

1, 2

L1/N

Supply connection, power supply; for nominal voltage range see technical data

PE

PE

PE

Ground connection, PE connection

KL2

1

NO

Status relay, floating status contact, make for failure

KL2

2

COM

Status relay, floating status contact, changeover contact, common connection, contact rating, max. 250 VAC/2
A (AC1)/min. 10 mA

KL2

3

NC

Status relay, floating status contact, break for failure

KL3

1

RSA

Bus connection RS485, RSA, MODBUS-RTU; SELV

KL3

2

RSB

Bus connection RS485, RSB, MODBUS-RTU; SELV

KL3

3

GND

Reference ground for control interface, SELV

KL3

4

Ain1 U

Analog input 1, set value: 0-10 V, Ri = 100 kΩ, adjustable curve, only usable as alternative to input Ain1 I;
SELV

KL3

5

+10 V

Fixed voltage output 10 VDC, +10 V ± 3%, max. 10 mA, short-circuit-proof, power supply for external
devices (e.g. pot); SELV

KL3

6

Ain1 I

Analog input 1, set value: 4-20 mA, Ri = 100 Ω, adjustable curve, only usable as alternative to input Ain1 U;
SELV

KL3

7

Din1

Digital input 1: enable electronics,
enable: pin open or applied voltage 5-50 VDC
disable: bridge to GND or applied voltage < 1 VDC
reset function: triggers software reset after a level change to < 1 VDC; SELV

KL3

8

Din2

Digital input 2: Switching parameter sets 1/2, according to EEPROM setting, the valid or used parameter set
can be selected via bus or via digital input DIN2.
Parameter set 1: pin open or applied voltage 5-50 VDC
Parameter set 2: bridge to GND or applied voltage < 1 VDC; SELV

Item no. 57535-5-9970 · ENU · Change 230627 · Approved 2022-02-07 · Page 9 / 14

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K3G310-PG93-21

Page 1: ...zed specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associ...

Page 2: ...eller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balanci...

Page 3: ...sing the device within the permitted ambient temperature range see Chapter 3 6 Transport and storage conditions and Chapter 3 2 Nominal data Operating the device with all protective devices Following...

Page 4: ...om rotor on top on request 2 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Tightening torque 3 5 0 5 Nm 4 Inlet ring with pressure tap k factor 116 5 Attachment holes for FlowGrid 253...

Page 5: ...nents e g inlet rings The dimensions must be requested from ebm papst If other air conduction geometries are used on the installation side the ebm papst evaluation loses its validity the conformity mu...

Page 6: ...d ambient temp for motor transport storage 40 C 4 CONNECTION AND STARTUP 4 1 Mechanical connection CAUTION Risk of cutting and crushing when removing device from packaging Carefully remove the device...

Page 7: ...at the minimum cable cross section is at least AWG 26 0 13 mm Protective earth contact resistance according to EN 61800 5 1 Compliance with the resistance specifications according to EN 61800 5 1 for...

Page 8: ...routing Water must be prevented from reaching the cable gland along the cable NOTE Damage caused by moisture penetration Moisture can penetrate into the terminal box if water is constantly present at...

Page 9: ...ly usable as alternative to input Ain1 I SELV KL3 5 10 V Fixed voltage output 10 VDC 10 V 3 max 10 mA short circuit proof power supply for external devices e g pot SELV KL3 6 Ain1 I Analog input 1 set...

Page 10: ...only usable as alternative to input Ain2 I SELV KL3 12 20 V Fixed voltage output 20 VDC 20 V 25 10 max 50 mA short circuit proof power supply for external devices e g sensors SELV Alternatively 24 VD...

Page 11: ...ossibly resonant frequencies must be determined in the course of fan commissioning Either run through the resonant range as quickly as possible with speed control or find another remedy Operation with...

Page 12: ...am Motor electronics overtemperature Deficient cooling Improve cooling Let the device cool down To reset the error message switch off the line voltage for at least 25 s and then switch it on again The...

Page 13: ...n measurement Recommended every 6 months Clean impeller or replace device 6 4 Disposal For ebm papst environmental protection and resource preservation are top priority corporate goals ebm papst opera...

Page 14: ...pose of electronic components employing the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 57535 5 9970 ENU Change 230627 Approved 2022 02...

Reviews: