ebm-papst K3G250-AV29-B6 Operating Instructions Manual Download Page 5

Operating instructions

K3G250-AV29-B6

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G084-FA

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 277

Frequency / Hz

50/60

Method of obtaining
data

ml

Speed (rpm) / min

-1

3450

Power consumption / W

750

Current draw / A

3.3

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

40

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to Commission Regulation (EU) 327/
2011

Actual

Req. 2015

01 Overall efficiency η

es

/ %

62.5

50.2

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

74.3

62

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart
· HRA 590344
D-74673 Mulfingen

08 Type

K3G250-AV29-B6

09 Power consumption P

ed

/ kW

0.75

09 Air flow q

v

/ m³/h

1755

09 Pressure increase total p

sf

/

Pa

889

10 Speed (rpm) n / min

-1

3490

11 Specific ratio

*

1.01

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller

combination in a standardized measurement setup.

3.4 Technical description

Weight

10.5 kg

Size

250 mm

Motor size

84

Rotor surface

Painted black

Electronics housing
material

Die-cast aluminum, painted black

Impeller material

Sheet aluminum, coated with white plastic

Support plate material

Sheet steel, galvanized and painted white

Support bracket
material

Steel, galvanized and painted black

Inlet nozzle material

Sheet steel, galvanized and painted white

Number of blades

7

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP54

Insulation class

"B"

Moisture (F) /
Environmental (H)
protection class

H2+S

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Output for slave 0-10 V
- Input for sensor 0-10 V or 4-20 mA
- Alarm relay
- Motor current limitation
- PFC, active
- RS-485 MODBUS-RTU
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from supply
- Thermal overload protection for
electronics/motor
- Line undervoltage / phase failure
detection

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Electrical hookup

Terminal box

Motor protection

Thermal overload protector (TOP)
internally connected

Protection class

I (if protective earth is connected by
customer to the housing's connection point)

Conformity with
standards

EN 61800-5-1; CE

Approval

EAC

Item no. 51316-5-9970 · ENU · Change 213957 · Approved 2020-07-14 · Page 5 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K3G250-AV29-B6

Page 1: ...permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the devic...

Page 2: ...t DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until al...

Page 3: ...be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fa...

Page 4: ...Cable diameter min 4 mm max 10 mm tightening torque 2 5 0 4 Nm 2 Inlet ring with pressure tap k factor 70 3 Tightening torque 3 5 0 5 Nm Item no 51316 5 9970 ENU Change 213957 Approved 2020 07 14 Pag...

Page 5: ...ined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 10 5 kg Size 250 mm Motor size 84 Rotor surface Painted black Electronics housing material...

Page 6: ...ing Carefully remove the device from the packaging by grasping hold of the frame Never subject to any impact Wear safety shoes and cut resistant safety gloves CAUTION Heavy load when unpacking device...

Page 7: ...the device voltage Only use cables designed for the current level indicated on the nameplate For determining the cross section note the sizing criteria according to EN 61800 5 1 The protective earth m...

Page 8: ...ables are fed in Route the wire s not included in scope of delivery into the terminal box First connect the PE protective earth Connect the wires to the corresponding terminals Use a screwdriver to do...

Page 9: ...eter set 2 PWM control Fan device address 01 Max PWM 100 Min PWM 8 0 Save set value to EEPROM No Set value requirement Analog linear Direction of action parameter set 1 Positive heating Direction of a...

Page 10: ...tion level KL3 2 8 GND Reference ground for control interface SELV KL3 3 7 0 10 V Control current sensor value input 0 10 VDC impedance 100 k use only as alternative to 4 20 mA input SELV KL3 4 10 V V...

Page 11: ...witching off the device for maintenance Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the power sup...

Page 12: ...e motor Soiling of the impeller can cause vibration that will shorten the service life of the fan Severe vibration can destroy the fan In such cases switch off the fan immediately and clean it The pre...

Page 13: ...mbly of the product must be performed or supervised by qualified personnel with the appropriate technical knowledge The product is to be disassembled into suitable components for disposal employing st...

Reviews: