3.2 Nominal data

Motor

M2E068-EC

Phase

1~

1~

Nominal voltage / VAC

230

230

Frequency / Hz

50

60

Method of obtaining
data

ml

ml

Valid for approval/
standard

-

-

Speed (rpm) / min

-1

2500

2450

Power consumption / W

210

285

Current draw / A

0.93

1.25

Capacitor / µF

5

5

Capacitor voltage / VDB

400

400

Min. back pressure / Pa

0

0

Min. ambient
temperature / °C

-25

-25

Max. ambient
temperature / °C

70

30

Starting current / A

1.5

1.4

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Technical description

Weight

3.7 kg

Fan size

250 mm

Rotor surface

Painted black

Impeller material

PA plastic

Housing material

PA plastic

Number of blades

7

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP44; installation- and position-dependent
as per EN 60034-5

Insulation class

"F"

Moisture (F) /
Environmental (H)
protection class

H1

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

< 0.75 mA

Electrical hookup

With plug

Motor protection

Thermal overload protector (TOP)
internally connected

with cable

Variable

Protection class

I (with customer connection of protective
earth)

Motor capacitor
according to EN 60252-
1 in safety protection
class

S0

Conformity with
standards

EN 60335-1

Approval

UL 1004-3; CSA C22.2 No. 77

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. This does not however in any way affect the
technical properties of the products. The product is to be protected against
UV radiation to prevent the formation of patches and fading. Changes in
color are not a reason for complaint and are not covered by the warranty.

3.4 Mounting data

Strength class of
screws

8.8

For screw clearance, see Chapter 3.1 Product drawing

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

Any further mounting data required can be taken from the product
drawing or Section Chapter 4.1 Mechanical connection.

3.5 Transport and storage conditions

Max. permitted
ambient temp. for
motor (transport/
storage)

+ 80 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

- 40 °C

Item no. 11921-5-9970 · ENU · Change 96928 · Approved 2017-10-26 · Page 5 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K2E250-RA50-11

Page 1: ...ed and otherwise used by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the el...

Page 2: ...coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating de...

Page 3: ...s Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Reson...

Page 4: ...ug pin tyco 350218 1 Mating connector not included in scope of delivery 4 pole connector housing tyco 926298 6 4x socket tyco 926 884 1 1 1 PE 1 2 L 1 3 N capacitor 1 4 Capacitor capacitor connected i...

Page 5: ...protection class S0 Conformity with standards EN 60335 1 Approval UL 1004 3 CSA C22 2 No 77 With regard to cyclic speed loads note that the rotating parts of the device are designed for a maximum of o...

Page 6: ...d back on NOTE Water ingress into wires or cables Water ingress at the customer end of the cable can damage the device Make sure the end of the cable is connected in a dry environment Only connect the...

Page 7: ...your connector s pin assignment Connect the built in connector with the mating connector Ensure that the connector is properly engaged Item no 11921 5 9970 ENU Change 96928 Approved 2017 10 26 Page 7...

Page 8: ...instructions 4 4 Connection diagram L blue N black PE green yellow Item no 11921 5 9970 ENU Change 96928 Approved 2017 10 26 Page 8 10 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phon...

Page 9: ...necting be sure to disconnect the ground connection last 5 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Send the device to ebm papst for repair or re...

Page 10: ...ents Always observe the applicable country specific legal regulations with regard to the disposal of products or waste occurring in the various phases of the life cycle The corresponding disposal stan...

Reviews: