ebm-papst G3G146-FH23-01 Operating Instructions Manual Download Page 8

Operating instructions

G3G146-FH23-01

Translation of the original operating instructions

4.4 Connection diagram

Drawing preliminary!

No.

Conn.

Designation

Color

Function/assignment

CON10 L

black

Power supply 230 VAC, 50-60 Hz, see nameplate for voltage range

CON11 N

blue

Neutral conductor

CON12 PE

green/
yellow

Protective earth

1

GND

blue

GND connection for control interface

2

0-10V PWM

yellow

Control input 0-10 V or PWM, electrically isolated

3

10 V / max. 1,1
mA

red

Voltage output 10 VDC 1.1 mA, electrically isolated, short-circuit-proof

4

Tacho

white

Tach output: open collector, 1 pulse per revolution, electrically isolated

Item no. 51504-5-9970 · ENU · Change 96553 · Approved 2017-10-26 · Page 8 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for G3G146-FH23-01

Page 1: ...authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basi...

Page 2: ...Electrical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury...

Page 3: ...ons Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Res...

Page 4: ...dimensions in mm 1 Cable PVC AWG20 3x crimped splices 2 Cable PVC AWG22 4x crimped splices 3 For self tapping M4 screws Item no 51504 5 9970 ENU Change 96553 Approved 2017 10 26 Page 4 11 ebm papst Mu...

Page 5: ...for a maximum of one million load cycles If you have special questions consult ebm papst for support Use the device in accordance with its degree of protection Information on surface quality The surf...

Page 6: ...n the device secure the system machine in which the device is installed so as to prevent it from being switched back on NOTE Water ingress into wires or cables Water ingress at the customer end of the...

Page 7: ...urrent FLA 4 3 Connecting the cables The device has external leads First connect the PE protective earth Connect the cables according to your application When doing so observe Chapter 4 4 Connection d...

Page 8: ...ve earth 1 GND blue GND connection for control interface 2 0 10V PWM yellow Control input 0 10 V or PWM electrically isolated 3 10 V max 1 1 mA red Voltage output 10 VDC 1 1 mA electrically isolated s...

Page 9: ...e g in cyclic operation on and off via power supply Disconnect the device from the power supply When disconnecting be sure to disconnect the ground connection last 5 INTEGRATED PROTECTIVE FEATURES Th...

Page 10: ...n standards Right from the development stage ecological design technical safety and health protection are fixed criteria The following section contains recommendations for ecological disposal of the p...

Page 11: ...mploying the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 51504 5 9970 ENU Change 96553 Approved 2017 10 26 Page 11 11 ebm papst Mulfinge...

Reviews: