background image

Operating instructions

G3G146-AB72-01

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G074-CF

Phase

1~

Nominal voltage / VAC

115

Frequency / Hz

50/60

Method of obtaining
data

ml

Status

prelim.

Speed (rpm) / min

-1

2390

Power consumption / W

170

Current draw / A

2.1

Min. back pressure / Pa

0

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

60

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Technical description

Weight

3.5 kg

Size

146 mm

Motor size

74

Rotor surface

Thick-film passivated

Electronics housing
material

Die-cast aluminum

Impeller material

Sheet steel, galvanized

Housing material

Die-cast aluminum

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP44; installation- and position-dependent
as per EN 60034-5

Insulation class

"B"

Moisture (F) /
Environmental (H)
protection class

H1

Installation position

Shaft horizontal or rotor on top; rotor on
bottom on request

Condensation
drainage holes

None

Mode

Continuous operation (S1)

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 1.1 mA
- Tach output
- Power limiter
- Motor current limitation
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Thermal overload protection for motor

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Motor protection

Thermal overload protector (TOP)
internally connected

with cable

Variable

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 60335-1

Approval

UL 1004-3 + 60730-1; CSA C22.2 No.
77 + CAN/CSA-E60730-1

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. This does not however in any way affect the
technical properties of the products. The product is to be protected against
UV radiation to prevent the formation of patches and fading. Changes in
color are not a reason for complaint and are not covered by the warranty.

3.4 Mounting data

For screw clearance, see Chapter 3.1 Product drawing

Strength class of
screws

8.8

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

Any further mounting data required can be taken from the product
drawing or Section Chapter 4.1 Mechanical connection.

3.5 Transport and storage conditions

Max. permitted
ambient temp. for
motor (transport/
storage)

+ 80 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

- 40 °C

3.6 Electromagnetic compatibility

EMC immunity to
interference

According to EN 61000-6-2

EMC interference
emission

According to EN 55022 (Class B)

Item no. 51254-5-9970 · ENU · Change 200166 · Approved 2019-06-17 · Page 5 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for G3G146-AB72-01

Page 1: ...authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basi...

Page 2: ...lectrical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury...

Page 3: ...prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration...

Page 4: ...imensions in mm 1 Cable PVC AWG18 3x crimped ferrules 2 Cable PVC AWG22 4x crimped ferrules 3 For self tapping M4 screws Item no 51254 5 9970 ENU Change 200166 Approved 2019 06 17 Page 4 11 ebm papst...

Page 5: ...h standards EN 60335 1 Approval UL 1004 3 60730 1 CSA C22 2 No 77 CAN CSA E60730 1 With regard to cyclic speed loads note that the rotating parts of the device are designed for a maximum of one millio...

Page 6: ...OTE Water ingress into wires or cables Water ingress at the customer end of the cable can damage the device Make sure the end of the cable is connected in a dry environment Only connect the device to...

Page 7: ...protection the starting current LRA is equal to or less than the nominal current FLA 4 3 Connecting the cables The device has external leads First connect the PE protective earth Connect the cables ac...

Page 8: ...en yellow Ground connection 8 0 10 V PWM yellow 0 10 V PWM control input Ri 100 k SELV 9 Tacho white Tach output open collector 1 pulse per revolution Isink max 10 mA SELV 11 10 V red Fixed voltage ou...

Page 9: ...connecting be sure to disconnect the ground connection last 5 INTEGRATED PROTECTIVE FEATURES The integrated protective functions cause the motor to switch off automatically in the event of the faults...

Page 10: ...e fan for 2 hours at maximum speed to permit the evaporation of any moisture that may have ingressed If cleaning does not eliminate vibrations the fan may need to be rebalanced To have it rebalanced c...

Page 11: ...tallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plasti...