ebm-papst G3G125-AA20-10 Operating Instructions Manual Download Page 5

Operating instructions

G3G125-AA20-10

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G074-BF

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

208 .. 250

Frequency / Hz

50/60

Type of data definition

me

Speed / min

-1

13000

Power input / W

600

Current draw / A

2.6

Min. ambient temperature
/ °C

-25

Max. ambient
temperature
/ °C

50

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Technical features

Mass

4.0 kg

Size

125 mm

Surface of rotor

Coated in black

Material of impeller

Aluminium sheet

Number of blades

6

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP 20

Insulation class

"B"

Mounting position

Any

Condensate discharge
holes

None

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Tach output
- Motor current limit
- PFC, active
- Soft start
- Control input 0-10 VDC / PWM
- Over-temperature protected
electronics / motor

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical leads

With plug

Motor protection

Locked-rotor protection

Product conforming
to standard

EN 61800-5-1; CE

Approval

VDE; UL 507; CSA C22.2 Nr.113

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.4 Mounting data

For depth of screw, see chapter 3.1 Product drawing

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.5 Transport and storage conditions

;

Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+ 80 °C

Min. permissible
ambient motor temp.
(transp./storage)

- 40 °C

3.6 Electromagnetic compatibility

EMC interference
immunity

Acc. to EN 61000-6-2

EMC harmonics

Acc. to EN 61000-3-2/3

EMC interference
emission

Acc. to EN 61000-6-4 (industrial
environment)

Item no. 50979-5-9970 · Revision 81898 · Release 2014-02-12 · Page 5 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for G3G125-AA20-10

Page 1: ...y authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazar...

Page 2: ...t the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental con...

Page 3: ...the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving highl...

Page 4: ...ng All measures have the unit mm 1 Connector housing WAGO 231 106 1 1 Tach 1 2 GND 1 3 PWM 0 10 V 1 4 PE 1 5 N 1 6 L Item no 50979 5 9970 Revision 81898 Release 2014 02 12 Page 4 10 ebm papst Mulfinge...

Page 5: ...ectrical leads With plug Motor protection Locked rotor protection Product conforming to standard EN 61800 5 1 CE Approval VDE UL 507 CSA C22 2 Nr 113 For cyclic speed loads note that the rotating part...

Page 6: ...ted in a dry environment Connect the device only to circuits that can be switched off using an all pole disconnecting switch 4 2 1 Prerequisites Check whether the data on the type plate agree with the...

Page 7: ...iginal operating instructions 4 4 Connection screen Item no 50979 5 9970 Revision 81898 Release 2014 02 12 Page 7 10 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 F...

Page 8: ...heck the air flow paths of the fan for foreign objects and remove any that are found Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4 7 Switching off the...

Page 9: ...ise correct connection see connection diagram Overtemperature of electronics motor Insufficient cooling Improve cooling Let the device cool down To reset the error message switch off the mains supply...

Page 10: ...insulation of the wires for damage Visual inspection At least every 6 months Replace wires Item no 50979 5 9970 Revision 81898 Release 2014 02 12 Page 10 10 ebm papst Mulfingen GmbH Co KG Bachm hle 2...

Reviews: