ebm-papst G2D120-AA04-01 Operating Instructions Manual Download Page 6

Operating instructions

G2D120-AA04-01

Translation of the original operating instructions

CAUTION
Voltage

The device is a built-in component and has no disconnecting
switch.
→ Only connect the device to circuits that can be switched off

with an all-pole disconnection switch.

→ When working on the device, secure the system/

machine in which the device is installed so as to prevent it
from being switched back on.

NOTE
Water ingress into wires or cables

Water ingress at the customer end of the cable can damage the
device.
→ Make sure the end of the cable is connected in a dry

environment.

Only connect the device to circuits that can be switched off with
an all-pole disconnection switch.

4.2.1 Requirements

;

Check whether the data on the nameplate match the connection data.

;

Before connecting the device, make sure the power supply matches
the device voltage.

;

Only use cables designed for the current level indicated on the
nameplate.
For determining the cross-section, note the sizing criteria according
to EN 61800-5-1. The protective earth must have a cross-section
equal to or greater than that of the phase conductor.
We recommend the use of 105 °C cables. Ensure that the minimum
cable cross-section is at least
AWG 26 / 0.13 mm².

Ground conductor contact resistance according to EN 60335

Compliance with the impedance specifications according to EN 60335
for the protective earth connection circuit must be verified in the end
application.
Depending on the circumstances of installation, it may be necessary to
connect an additional protective earth conductor to the extra protective
earth terminal on the device.

4.2.2 Voltage control

With speed control using transformers or electronic voltage
regulators (e.g. phase control), excessive current may occur.
In addition, depending on how the device is installed, noises
can occur with phase control.

4.2.3 Variable frequency drive

Please use a variable frequency drive only after consultation with ebm-
papst.

For operation with variable frequency drives, install sinusoidal
filters that work on all poles (phase-phase and phase-ground)
between the drive and the motor.
During operation with variable frequency drives, an all-pole
sine filter protects the motor against high-voltage transients that
can destroy the coil insulation system, and against harmful
bearing currents.

Heating of the motor due to use of a variable frequency drive must be
checked in the application by the customer.

4.3 Connecting the cables

The device has external leads.

;

First connect the "PE" (protective earth).

Connect the cables according to your application. When doing so,
observe Chapter 4.4 Connection diagram.

4.3.1 Motor protection

WARNING
Device has no overheating protection

The device is supplied without any automatic overheating
protection. The device can become hot and catch fire.
→ For the version without thermal overload protector, also

install a suitable motor protection switch.

Item no. 12036-5-9970 · ENU · Change 89188 · Approved 2016-04-18 · Page 6 / 9

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for G2D120-AA04-01

Page 1: ...only be transported unpacked installed operated maintained and otherwise used by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the dev...

Page 2: ...contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled a...

Page 3: ...ta Operating the device with all protective devices Following the operating instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Oper...

Page 4: ...AL DATA 3 1 Product drawing All dimensions in mm 1 Cable PVC 7G 0 5 mm 7x crimped splices Item no 12036 5 9970 ENU Change 89188 Approved 2016 04 18 Page 4 9 ebm papst Mulfingen GmbH Co KG Bachm hle 2...

Page 5: ...apst for support 3 4 Mounting data For screw clearance see Chapter 3 1 Product drawing Secure the screws against unintentional loosening e g use self locking screws Strength class of screws 8 8 Any fu...

Page 6: ...cumstances of installation it may be necessary to connect an additional protective earth conductor to the extra protective earth terminal on the device 4 2 2 Voltage control With speed control using t...

Page 7: ...two phases Three phase motor Delta connection Y Star connection L1 U1 black L2 V1 blue L3 W1 brown U2 green V2 white W2 yellow PE green yellow Item no 12036 5 9970 ENU Change 89188 Approved 2016 04 1...

Page 8: ...otor restarts automatically when operating voltage is applied e g after a power failure Risk of injury Keep out of the device s danger zone When working on the device switch off the line voltage and e...

Page 9: ...ualified personnel with the appropriate technical knowledge The product is to be disassembled into suitable components for disposal employing standard procedures for motors WARNING Heavy parts of the...