Operating instructions
G1G170-AB53-01
Translation of the original operating instructions
4.4 Connection diagram
No.
Pin
Signal
Function / assignment
ST1
1, 2, 3 L, N, PE
Power supply 230 VAC, 50-60 Hz, neutral conductor, protective earth
ST2
1
UB
External voltage 24-45 VDC
ST2
2
DUE
Speed monitoring output connection, monitoring circuit output, 3 pulses per revolution, current source 1 mA
ST2
3
N.C
Not assigned
ST2
4
PWM
PWM - 2 - 6 kHz control input, PWM on n = 100%, PWM low n = 0%
ST2
5
GND
GND - Connection for control interface
Item no.: 51047-5-9970 · Revision: 75315 · Print-out: 2012-04-11 · Y. Uhlmann (VM-TDO) · Page 9 / 12