ebm-papst G1G126-AA45-71 Operating Instructions Manual Download Page 9

Operating instructions

G1G126-AA45-71

Translation of the original operating instructions

4.5 Checking the connections

;

Make sure that the power is off (all phases).

;

Secure it from being switched on again.

;

Check the correct fit of the connection lines.

4.6 Switch on device

The device may only be switched on if it has been installed properly and
in accordance with its intended use, including the required safety
mechanisms and professional electrical connection. This also applies for
devices which have already been equipped with plugs and terminals or
similar connectors by the customer.

WARNING
Hot motor housing

Fire hazard
→ Ensure that no combustible or flammable materials are

located close to the blower.

;

Inspect the device for visible external damage and the proper function
of the protective features before switching it on.

;

Check the air flow paths of the fan for foreign objects and remove any
that are found.

;

Apply 0 VDC to the 0-10 V control input (if you are using the control
input)

;

Apply 0 % PWM to the PWM control input (if you are using the
PWM control input)

;

Apply the nominal voltage to the voltage supply.

;

Start the device by changing the input signal.

4.7 Switching off the device

Switching off the device during operation:

;

Switch on the device via the control input.

;

Do not switch the motor (e.g. in cyclic operation) on and off via power
supply.

Switching off the device for maintenance work:

;

Switch on the device via the control input.

;

Do not switch the motor (e.g. in cyclic operation) on and off via power
supply.

;

Disconnect the device from the supply voltage.

;

When disconnecting, be sure to disconnect the earth wire connection
last.

5. INTEGRATED PROTECTIVE FUNCTIONS

The integrated protective functions cause the motor to switch off
automatically in case of faults described in the table.

Malfunctions

Description / Function of
safety feature

Rotor position detection error

An automatic restart occurs.

Locked rotor

;

After the blockage is

removed, the motor restarts
automatically.

Item no. 51282-5-9970 · Revision 79946 · Release 2013-12-02 · Page 9 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for G1G126-AA45-71

Page 1: ... authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modifications additions or conversions to the devi...

Page 2: ...trically live parts Escaping gas may also cause explosions Never open the blower WARNING Rotating device Long hair loose items of clothing and jewellery could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect long hair by wearing a cap WARNING Flying parts Missing safety devices may cause fan blades ...

Page 3: ...tems Installing the device into an overall system for moving air Commissioning the built in component only after installation in the customer unit Operating the device with all protective features in place Improper use Using the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving a medium t...

Page 4: ...o No 350 766 1 female terminal tyco No 926 884 1 2 1 L 2 2 N 2 3 PE 3 5 pole strip mating connector not included in delivery Molex No 39 01 4050 female connector Molex No 39 00 0059 3 1 3 2 Speed monitoring 3 3 Not assigned 3 4 PWM input 3 5 GND 4 Bleeder connection for pressure relief possible Item no 51282 5 9970 Revision 79946 Release 2013 12 02 Page 4 11 ebm papst Mulfingen GmbH Co KG Bachmühl...

Page 5: ...re Motor bearing Ball bearing Technical features Tach output Motor current limit Control input PWM Touch current acc IEC 60990 measuring network Fig 4 TN system 3 5 mA Motor protection Reverse polarity and locked rotor protection Remark Complete unit must be tested for required approvals For cyclic speed loads note that the rotating parts of the device are designed for maximum one million load cyc...

Page 6: ...t in component and features no electrically isolating switch Connect the device only to circuits that can be switched off using an all pole disconnecting switch When working on the device you must switch off the system machine in which the device is installed and secure it from being switched on again NOTE Water penetration into leads or wires Water enters at the cable end on the customers side an...

Page 7: ...your connector Connect the panel connector and mating connector Ensure that the connector is locked in correctly Item no 51282 5 9970 Revision 79946 Release 2013 12 02 Page 7 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 8: ...riginal operating instructions 4 4 Connection screen Item no 51282 5 9970 Revision 79946 Release 2013 12 02 Page 8 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 9: ...ly 0 PWM to the PWM control input if you are using the PWM control input Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4 7 Switching off the device Switching off the device during operation Switch on the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching off the device for maintenance wo...

Page 10: ...e if imbalance is still evident after cleaning replace the device If you have attached any weight clips during cleaning make sure to remove them afterwards Motor does not turn Mechanical blockage Switch off de energise and remove mechanical blockage Mains supply voltage faulty Check mains supply voltage restore power supply apply control signal Faulty connection De energise correct connection see ...

Page 11: ...f protective earth connection Visual inspection At least every 6 months Fasten Check the insulation of the wires for damage Visual inspection At least every 6 months Replace wires Condensate discharge holes for clogging as necessary Visual inspection At least every 6 months Open bore holes Item no 51282 5 9970 Revision 79946 Release 2013 12 02 Page 11 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 ...

Reviews: