Operating instructions

D3G280-GG10-01

Translation of the original operating instructions

4.5 Connection diagram

Drawing preliminary!

No.

Conn.

Designation

Color

Function/assignment

1

1, 2

PE

green/
yellow

Protective earth

1

3, 4, 5

L1, L2, L3

black

Power supply 50 / 60 Hz

1

6

NC

white 1

Status relay, floating status contact, break for failure; contact rating 250 VAC / 2 A (AC1) / min. 10
mA,
reinforced insulation on supply side and basic insulation on control interface side (or reinforced
insulation on control interface side up to 250 VAC potential difference)

1

7

COM

white 2

Status relay, floating status contact, break for failure; contact rating 250 VAC / 2 A (AC1) / min. 10
mA,
reinforced insulation on supply side and basic insulation on control interface side (or reinforced
insulation on control interface side up to 250 VAC potential difference)

2

9

+10 V

red

Fixed voltage output 10 VDC, SELV, +10 V ±3%, max. 10 mA, short-circuit-proof, power supply
for external devices (e.g. pot);
fixed voltage input 24 VDC for setting parameters via MODBUS without line voltage supply

2

10

0-10 V

yellow

Analog input (set value) SELV, 0-10 V, Ri = 100 kΩ, adjustable curve

2

11

RSA

white

RS485 interface for MODBUS, RSA; SELV

2

12

RSB

brown

RS485 interface for MODBUS, RSB; SELV

2

13

GND

blue

Reference ground for control interface, SELV

Item no. 54190-5-9970 · ENU · Change 260673 · Approved 2022-06-23 · Page 9 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for D3G280-GG10-01

Page 1: ...pecialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product The locally applicable industrial safety regulations are always to be observed when working on the device Keep the wo...

Page 2: ...nt DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and be pulled into the device Injuries can result Do not w...

Page 3: ...wing the operating instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan from the customer installation Operation in medical equipment with a lif...

Page 4: ... 10 V 2 4 0 10 V 2 5 GND 2 6 RSA 2 7 RSB 2 8 L1 2 9 L2 2 10 L3 3 Cable diameter min 8 mm max 12 mm tightening torque 1 8 0 3 Nm 4 Inlet ring with pressure tap k factor 175 on both sides Item no 54190 5 9970 ENU Change 260673 Approved 2022 06 23 Page 4 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ...uction geometries are used on the installation side the ebm papst evaluation loses its validity the conformity must be confirmed again The product does not fall within the scope of Regulation EU 2019 1781 due to the exception specified in Article 2 2a motors completely integrated into a product 3 4 Technical description Weight 19 6 kg Size 280 mm Motor size 84 Rotor surface Painted black Electroni...

Page 6: ...lity of the installation engineer or operator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected to a connection point with an Ssc value greater than or equal to 250 times the rated output of the arrangement 4 CONNECTION AND STARTUP 4 1 Mechanical connection CAUTION Cutting and crushing hazard when removing blower from packagi...

Page 7: ... reactive currents can be measured in the supply line even when the motor is at a standstill and the line voltage is switched on The values are typically in the range 250 mA At the same time the effective power in this operating state operational readiness is typically 5 W 4 2 4 Residual current circuit breaker RCCB If the use of a residual current device RCD is required in your installation only ...

Page 8: ...tly in front of the cable gland for example When routing the cable make sure that the cable glands are located at the bottom The cables must always be routed downward 4 4 Factory settings Factory settings made for the device by ebm papst Mode parameter set 1 PWM control Mode parameter set 2 PWM control Fan device address 1 Max PWM 100 Min PWM 5 1 Save set value to EEPROM No Set value requirement A...

Page 9: ... min 10 mA reinforced insulation on supply side and basic insulation on control interface side or reinforced insulation on control interface side up to 250 VAC potential difference 2 9 10 V red Fixed voltage output 10 VDC SELV 10 V 3 max 10 mA short circuit proof power supply for external devices e g pot fixed voltage input 24 VDC for setting parameters via MODBUS without line voltage supply 2 10 ...

Page 10: ...er supply Switching off the device for maintenance Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the power supply When disconnecting be sure to disconnect the ground connection last 5 INTEGRATED PROTECTIVE FEATURES The integrated protective functions cause the motor to switch off automatically in t...

Page 11: ...eaning To ensure a long service life check the fans regularly for proper operation and soiling The frequency of checking is to be adapted accordingly depending on the degree of soiling DANGER Risk of injury from rotating fan Only clean when not in motion Do not disconnect the fan from the power supply just switch it off via the control input This will prevent start up of the fan Dirt deposits on t...

Page 12: ...requirements NOTE Country specific legal requirements Always observe the applicable country specific legal regulations with regard to the disposal of products or waste occurring in the various phases of the life cycle The corresponding disposal standards are also to be heeded 6 3 2 Disassembly Disassembly of the product must be performed or supervised by qualified personnel with the appropriate te...

Reviews: