4.6 Checking connections
;
Ensure isolation from supply (all phases).
;
Make sure a restart is impossible
;
Check the cables for proper fit.
;
Screw the terminal box cover back on again. Terminal box tightening
torque, see Chapter 3.1 Product drawing.
;
Make sure the terminal box is completely closed and sealed and that
all screws and cable glands have been properly tightened.
4.7 Switching on the device
The device may only be switched on if it has been installed properly and
in accordance with its intended use, including the required safety
mechanisms and professional electrical hookup. This also applies for
devices which have already been equipped with plugs and terminals or
similar connectors by the customer.
WARNING
Hot motor housing
Risk of fire
→ Ensure that no combustible or flammable materials are
located close to the blower.
;
Before switching on, check the device for visible external damage
and make sure the protective devices are functional.
;
Check the fan's air flow paths for foreign matter and remove any
foreign matter found.
;
Apply the nominal supply voltage.
;
Start the device by changing the input signal.
NOTE
Damage to the device from vibration
Bearing damage, shorter service life
→ Low-vibration operation of the fan must be ensured over the
entire speed control range.
→ Severe vibration can arise for instance from inexpert
handling, transportation damage and resultant imbalance or
be caused by component or structural resonance.
→ Speed ranges with excessively high vibration levels and
possibly resonant frequencies must be determined in the
course of fan commissioning.
→ Either run through the resonant range as quickly as
possible with speed control or find another remedy.
→ Operation with excessively high vibration levels can
lead to premature failure.
4.8 Switching off the device
Switching off the device during operation:
;
Switch off the device via the control input.
;
Do not switch the motor (e.g. in cyclic operation) on and off via power
supply.
Switching off the device for maintenance:
;
Switch off the device via the control input.
;
Do not switch the motor (e.g. in cyclic operation) on and off via power
supply.
;
Disconnect the device from the power supply.
;
When disconnecting, be sure to disconnect the ground connection last.
4.9 Disconnection of supply line from device
Heed the following if the supply line has to be disconnected from the
device:
●
Switch off the device via the control input.
●
Disconnect the device from the power supply.
●
Ensure safe isolation from supply (all phases).
●
Secure against restarting
●
Unfasten the cable glands.
●
Slacken off and screw out the four terminal box screws.
●
Detach the terminal box cover.
●
Disconnect the plugs by sliding a suitable object between the strip and
the header housing and release the retainer tab.
●
Pull out the strip at the cable.
●
On assembly, slide the strip into the header housing until it engages.
●
Fit the terminal box cover.
●
Tighten the cable glands.
●
Make sure the terminal box is completely closed and sealed and that
all screws and cable glands have been properly tightened (see
product drawing for tightening torques).
5. INTEGRATED PROTECTIVE FEATURES
The integrated protective functions cause the motor to switch off
automatically in the event of the faults described in the table.
Fault
Safety feature description/
function
Rotor position detection error
An automatic restart follows.
Blocked rotor
;
After the blockage is
removed, the motor restarts
automatically.
Line undervoltage (line voltage
outside of permitted nominal
voltage range)
;
If the line voltage returns to
permitted values, the motor
restarts automatically.
Item no. 54390-5-9970 · ENU · Change 257332 · Approved 2022-09-08 · Page 10 / 12