ebm-papst D3G146-AH50-11 Operating Instructions Manual Download Page 10

Operating instructions

D3G146-AH50-11

Translation of the original operating instructions

Faulty connection

De-energise, correct
connection, see
connection diagram.

Overtemperature of
electronics/motor

Insufficient cooling

Improve cooling. Let
the device cool down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.

Thermal overload
protector responded

Allow motor to cool
off, locate and rectify
cause of error, if
necessary cancel
restart lock-out

Ambient temperature
too high

Reduce the ambient
temperature.
Reset by reducing
control input to 0.

Unacceptable
operating point

Correct the operating
point. Let the device
cool down.

If you have any other problems, contact ebm-papst.

6.1 Cleaning

To ensure a long service life, the fans have to be regularly checked for
proper operation and degree of soiling. The frequency of the checks is to
be adapted to the occurrence of soiling.

DANGER
Risk of injury from rotating fan.

→ Only clean when not in motion. Do not disconnect the fan

from the power supply, just switch it off via the control input.
This will prevent start-up of the fan.

;

Dirt deposits on the motor housing could lead to overheating of the
motor.

;

Dirt on the impeller can cause vibration which would shorten the
service life of the fan.

;

Severe vibration could destroy the fan.

;

In such cases immediately switch off and clean the fan.

;

The preferred method of cleaning is dry cleaning, e.g. using
compressed air.

;

Use is never to be made of corrosive cleaning agents!

NOTE
Damage to the device during cleaning

Malfunction possible
→ Do not clean the device using a water jet or high-pressure

cleaner.

→ Do not use any acid, alkali or solvent-basedcleaning

agents.

→ Do not use any pointed or sharp-edged objects for cleaning

;

Completely remove any cleaning agents used.

;

Immediately switch off and replace the device if severe corrosion is
apparent at load-bearing or rotating parts.

;

Repairs to load-bearing or rotating parts are not permissible!

;

Operate the fan for 2 hours at maximum speed to permit the
evaporation of any water which may have ingressed.

;

If cleaning does not eliminate vibration, the fan may have to be re-
balanced. In such cases please contact ebm-papst.

;

The fan is provided with maintenance-free ball bearings. The lifetime
lubrication of the ball bearings is designed for a service life of 40,000
hours.

;

Please contact ebm-papst if bearing replacement is required after this
period.

;

Adapt the maintenance intervals to the dust pollution occurring.

6.2 Safety test

NOTE
High-voltage test

The integrated EMC filter contains Y capacitors. Therefore, the
trigger current is exceeded when AC testing voltage is applied.
→ Test the device with DC voltage when you carry out the

high-voltage test required by law. The voltage to be used
corresponds to the peak value of the AC voltage required by
the standard.

What has to
be tested?

How to test?

Frequency

Which
measure?

Check the
protective
casing against
accidental
contact for
damage and to
ensure that it is
intact

Visual inspection At least every

6 months

Repair or
replacement of
the device

Check the
device for
damage to
blades and
housing

Visual inspection At least every

6 months

Replacement of
the device

Mounting the
connection lines

Visual inspection At least every

6 months

Fasten

Mounting of
protective earth
connection

Visual inspection At least every

6 months

Fasten

Check the
insulation of the
wires for damage

Visual inspection At least every

6 months

Replace wires

Impeller for
wear/deposits/
corrosion and
damage

Visual inspection At least every

6 months

Clean impeller
or replace device

Abnormal
bearing noise

acoustic

At least every
6 months

Replace device

6.3 Disposal

For ebm-papst, environmental protection and resource preservation are
top priority corporate goals.
ebm-papst operates an environmental management system which is
certified in accordance with ISO 14001 and rigorously implemented
around the world on the basis of German standards.
Right from the development stage, ecological design, technical safety
and health protection are fixed criteria.

Item no. 50037-5-9970 · ENG · Revision 212353 · Release 2020-05-07 · Page 10 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for D3G146-AH50-11

Page 1: ...o install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device The local industrial safety regulations must always be observed when working on the device Keep the workplace clean and tidy Untidiness in the working a...

Page 2: ...n installations on the customer s side Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair dangling items of clothing j...

Page 3: ... and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also include vibrations that are transmitted from the customer system to the fan Operation in medical equipment with a life sustaining or lifesaving function Moving solids content in flow medium Painting the device Connections e g screws coming loo...

Page 4: ...measures have the unit mm 1 Connection line PVC AWG20 3x core end sleeve 2 Connection line PVC AWG22 4x core end sleeve Item no 50037 5 9970 ENG Revision 212353 Release 2020 05 07 Page 4 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ...ed Housing material Sheet steel galvanised Motor suspension Motor mounted with anti vibration on both sides Direction of rotation Clockwise seen on rotor Type of protection IP44 Insulation class B Humidity F environmental protection class H H1 Mounting position Shaft horizontal Condensation drainage holes None Operation mode S1 Motor bearing Ball bearing Technical features Output 10 VDC max 1 1 mA...

Page 6: ...to the substructure without distorting it Check the device for transport damage Damaged devices must no longer be installed Install the undamaged device according to your application CAUTION Possibility of damage to the device Serious damage may result if the device slips during assembly Keep the device fixed in position at the installation location until all attachment screws have been tightened ...

Page 7: ...ding to the type plate For determining the cross section follow the basic principles in accordance with EN 61800 5 1 The protective earth must have a cross section equal to or greater than the outer conductor cross section We recommend the use of 105 C cables Ensure that the minimum cable cross section is at least AWG26 0 13 mm Protective earth contact resistance as per EN 60335 Compliance with th...

Page 8: ...h 8 0 10 V PWM yellow Control input 0 10 V or PWM electrically isolated 9 Tach white Tach output open collector 1 pulse per revolution electrically isolated 11 10V max 1 1 mA red Voltage output 10 V max 1 1 mA electrically isolated 12 GND blue GND Connection for control interface Item no 50037 5 9970 ENG Revision 212353 Release 2020 05 07 Page 8 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 7467...

Page 9: ...the motor e g in cyclic operation on and off via power supply Disconnect the device from the supply voltage When disconnecting be sure to disconnect the earth wire connection last 5 INTEGRATED PROTECTIVE FUNCTIONS The integrated protective functions cause the motor to switch off automatically in case of faults described in the table Malfunctions Description Function of safety feature Rotor positio...

Page 10: ...vaporation of any water which may have ingressed If cleaning does not eliminate vibration the fan may have to be re balanced In such cases please contact ebm papst The fan is provided with maintenance free ball bearings The lifetime lubrication of the ball bearings is designed for a service life of 40 000 hours Please contact ebm papst if bearing replacement is required after this period Adapt the...

Page 11: ... mostly made of steel copper aluminium and plastic Metallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminium Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boa...

Reviews: