Operating instructions

D3G133-LT13-01

Translation of the original operating instructions

4.4 Connection diagram

Drawing preliminary!

No.

Conn.

Designation

Color

Function/assignment

CON10 L

black

Power supply 230 VAC, 50-60 Hz, see nameplate for voltage range

CON11 N

blue

Neutral conductor

CON12 PE

green/
yellow

Protective earth

1

GND

blue

GND connection for control interface

2

0-10V PWM

yellow

Control input 0-10 V or PWM, electrically isolated

3

10 V / max. 1,1
mA

red

Voltage output 10 VDC 1.1 mA, electrically isolated, short-circuit-proof

4

Tacho

white

Tach output: open collector, 1 pulse per revolution, electrically isolated

Item no. 51513-5-9970 · ENU · Change 201834 · Approved 2019-10-08 · Page 8 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for D3G133-LT13-01

Page 1: ...authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basi...

Page 2: ...y that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accide...

Page 3: ...prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration...

Page 4: ...20 3x splice 2 Cable PVC AWG22 4x splice 3 4x sheet metal nut for thread EN ISO 1478 ST4 8 min screw length 14 5 mm plus material thickness of mounting Item no 51513 5 9970 ENU Change 201834 Approved...

Page 5: ...ed loads note that the rotating parts of the device are designed for a maximum of one million load cycles If you have special questions consult ebm papst for support Use the device in accordance with...

Page 6: ...OTE Water ingress into wires or cables Water ingress at the customer end of the cable can damage the device Make sure the end of the cable is connected in a dry environment Only connect the device to...

Page 7: ...protection the starting current LRA is equal to or less than the nominal current FLA 4 3 Connecting the cables The device has external leads First connect the PE protective earth Connect the cables ac...

Page 8: ...ve earth 1 GND blue GND connection for control interface 2 0 10V PWM yellow Control input 0 10 V or PWM electrically isolated 3 10 V max 1 1 mA red Voltage output 10 VDC 1 1 mA electrically isolated s...

Page 9: ...e g in cyclic operation on and off via power supply Disconnect the device from the power supply When disconnecting be sure to disconnect the ground connection last 5 INTEGRATED PROTECTIVE FEATURES Th...

Page 10: ...ned for a service life of 40 000 hours If bearing replacement is necessary after that period contact ebm papst Adapt the maintenance intervals to the actual level of dust exposure 6 2 Safety inspectio...

Page 11: ...num Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Onl...

Reviews: