background image

Operating instructions

D2E146-HR93-03

Translation of the original operating instructions

4.5 Checking the connections

;

Make sure that the power is off (all phases).

;

Secure it from being switched on again.

;

Check that the mating connector is correctly locked into the panel
connector.

;

Check that the mating connector is correctly crimped to the
connection line.

4.6 Switch on device

The device is not to be switched on until it has been installed properly
and in accordance with its intended use, including the required protective
devices and professional electrical connection. This also applies to
devices which have already been equipped with plugs and terminals or
similar connectors by the customer.

WARNING
Hot motor housing

Fire hazard
→ Ensure that no combustible or flammable materials are

located close to the blower.

;

Inspect the device for visible external damage and the proper function
of the protective features before switching it on.

;

Check the air flow paths of the fan for foreign objects and remove any
that are found.

;

Apply the nominal voltage to the voltage supply.

NOTE
Damage to device by vibrations

Bearing damage, reduced service life
→ The fan must operate free of vibrations throughout its speed

control range.

→ Strong vibrations can result from improper handling,

imbalance resulting from damage during transport, or
component-induced or structural resonances.

→ When putting the fan into service, determine the speed

ranges with excessive vibration levels and also any
resonance frequencies that may be present.

→ When regulating the speed, pass through resonance

ranges as quickly as possible or find another remedy.

→ Operation at excessive vibration levels can lead to

premature failure.

4.7 Switching off the device

;

Disconnect the device from the supply voltage at the main switch for
the supply line.

;

When disconnecting, be sure to disconnect the earth wire connection
last.

5. MAINTENANCE, MALFUNCTIONS, POSSIBLE
CAUSES AND REMEDIES

Do not perform any repairs on your device. Return the device to ebm-
papst for repair or replacement.

WARNING
Terminals and connections have voltage even with a
unit that is shut off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION
Electrical load on the capacitor after device is switched off

Electric shock, risk of injury
→ Discharge the capacitors before working on the device.

CAUTION
The motor restarts automatically when operating voltage
is applied, e.g. after a power failure.

Danger of injury
→ Keep out of the danger zone of the device.
→ When working on the device, switch off the mains

supply voltage and secure the latter from being switched on
again.

→ Wait until the device stops.

If the device remains out of use for some time, e.g. when in
storage, we recommend switching the device on for at least
two hours to allow any condensate to evaporate and to move
the bearings.

Malfunction/error

Possible cause

Possible remedy

Impeller running
roughly

Imbalance in rotating
parts

Clean the device; if
imbalance is still
evident after cleaning,
replace the device.
If you have
attached any weight
clips during cleaning,
make sure to remove
them afterwards.

Motor does not turn

Mechanical blockage

Switch off, de-
energise, and
remove mechanical
blockage.

Mains supply voltage
faulty

Check mains supply
voltage,
restore power
supply.

Faulty connection

De-energise, correct
connection, see
connection diagram.

Thermal overload
protector responded

Allow motor to cool
off, locate and rectify
cause of error, if
necessary cancel
restart lock-out

Unacceptable
operating point

Check operating point

Overtemperature of
motor

Ambient temperature
too high

Lower ambient
temperature if possible

Item no. 11870-5-9970 · ENG · Revision 202174 · Release 2018-12-27 · Page 9 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for D2E146-HR93-03

Page 1: ...fied trained and authorised technical staff Only authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device The local industrial safety regulations must always be observed w...

Page 2: ...tal contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair dangling items of clothing jewellery and similar items can become entangled and be pulled into the device Risk of injury Do not wear any loose fitting or dangling clothing or jewellery while working on rotating parts Protect long hair with a cap 1 7 Emission WARNING Dep...

Page 3: ...y cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also include vibrations that are transmitted from the customer system to the fan Operation in medical equipment with a life sustaining or lifesaving function Moving solids content in flow medium Painting the device Connections e g screws coming loose duri...

Page 4: ...ug pin TE 926886 1 1 1 L step 1 1 2 L step 2 1 3 L step 3 1 4 L step 4 1 5 N 1 6 Protective earth 2 4 x sheet metal nut for thread EN ISO 1478 ST4 8 min screw length 14 5 mm plus thickness of mounting material Item no 11870 5 9970 ENG Revision 202174 Release 2018 12 27 Page 4 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst...

Page 5: ...335 1 CE Approval CCC EAC VDE For cyclic speed loads note that the rotating parts of the device are designed for maximum one million load cycles If you have specific questions contact ebm papst for support Use the device in accordance with its protection type Notes on surface quality The surfaces of the products conform to the generally applicable industrial standard The surface quality may vary d...

Page 6: ...ole disconnecting switch 4 2 1 Prerequisites Check that the data on the type plate match the connection data If the operating capacitor is not installed by ebm papst check whether the data of the operating capacitor match the data on the type plate Before connecting the device ensure that the supply voltage matches the operating voltage of the device Only use cables designed for current according ...

Page 7: ...heck the PIN assignment of your connector Connect the panel connector and mating connector Ensure that the connector is locked in correctly Item no 11870 5 9970 ENG Revision 202174 Release 2018 12 27 Page 7 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 8: ...ds switch must break the circuit 1 Step 1 min 2 Step 2 3 Step 3 4 Step 4 max 5 N 6 PE protective earth 7 Speed increase Item no 11870 5 9970 ENG Revision 202174 Release 2018 12 27 Page 8 11 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 9: ...disconnect the earth wire connection last 5 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Return the device to ebm papst for repair or replacement WARNING Terminals and connections have voltage even with a unit that is shut off Electric shock Wait five minutes after disconnecting the voltage at all poles before opening the device CAUTION Electrical...

Page 10: ...for damage and to ensure that it is intact Visual inspection At least every 6 months Repair or replacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At least every 6 months Fasten Mounting of protective earth connection Visual inspection At least every 6 months ...

Page 11: ... external rotor motors from ebm papst Mulfingen GmbH Co KG Ferrite magnets can be disposed of in the same way as normal iron and steel Electrical insulating materials on the product in cables and wires are made of similar materials and are therefore to be treated in the same manner The materials concerned are as follows Miscellaneous insulators used in the terminal box Power lines Cables for inter...

Reviews: