background image

Operating instructions

D2D160-BE02-14

Translation of the original operating instructions

3.2 Nominal data

Motor

M2D074-LA

Phase

3~

3~

3~

3~

Nominal voltage / VAC

230

230

400

400

Wiring

Δ

Δ

Y

Y

Frequency / Hz

50

60

50

60

Method of obtaining
data

ml

ml

ml

ml

Valid for approval/
standard

-

-

-

-

Speed / min

-1

2700

3000

2700

3000

Power consumption / W

700

1055

700

1055

Current draw / A

2.2

3.0

1.28

1.7

Min. back pressure / Pa

400

500

400

500

Min. ambient
temperature / °C

-25

-25

-25

-25

Max. ambient
temperature / °C

75

75

75

75

Starting current / A

9.25

9.6

5.34

5.54

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Technical description

Weight

10.82 kg

Fan size

160 mm

Rotor surface

Painted black

Impeller material

Sheet steel, galvanized

Housing material

Sheet steel, galvanized

Guard grille material

Steel, galvanized and coated with white-
aluminum plastic (RAL 9006)

Motor suspension

Motor vibration-damped on both sides

Direction of rotation

Counterclockwise, viewed toward rotor

Degree of protection

IP00

Insulation class

"F"

Moisture (F) /
Environmental (H)
protection class

F2-1

Installation position

Any

Condensation
drainage holes

None, open rotor

Mode

S1

Motor bearing

Ball bearing

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

< 0.75 mA

Electrical hookup

With plug

Motor protection

Thermal overload protector (TOP) with
basic insulation

with cable

Axial

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 60335-1

Approval

CCC; CSA C22.2 No. 100; EAC; UL
1004-1

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

3.4 Mounting data

For screw clearance, see Chapter 3.1 Product drawing

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

Strength class of
screws

8.8

Any further mounting data required can be taken from the product drawing.

3.5 Transport and storage conditions

;

Use the device in accordance with its degree of protection.

Max. permitted
ambient temp. for
motor (transport/
storage)

+ 80 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

- 40 °C

4. CONNECTION AND STARTUP

4.1 Mechanical connection

CAUTION
Cutting and crushing hazard when removing blower
from packaging

→ Carefully remove the blower from its packaging, touching

only the housing. Strictly avoid shocks.

→ Wear safety shoes and cut-resistant safety gloves.

CAUTION
Heavy load when unpacking device

Risk of physical injury, such as back injuries.
→ Two people should work together to remove the device from

its packaging.

;

Check the device for transport damage. Damaged devices are not to
be installed.

;

Install the undamaged device in accordance with your application.

CAUTION
Possible damage to the device

If the device slips during installation, serious damage can result.
→ Ensure that the device is securely positioned at its place of

installation until all fastening screws have been tightened.

Item no. 12477-5-9970 · ENU · Change 89188 · Approved 2016-04-18 · Page 5 / 9

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for D2D160-BE02-14

Page 1: ...nsported unpacked installed operated maintained and otherwise used by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following instal...

Page 2: ...cal or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rota...

Page 3: ...Chapter 3 2 Nominal data Operating the device with all protective devices Following the operating instructions Improper use In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Conveying air that contains abrasive particles Conveying highly corrosive air e g salt spray Exc...

Page 4: ...ader Weidmüller STV S 9 SS and 9x crimped splices 1 1 black 1 2 blue 1 3 brown 1 4 gray 1 5 green yellow 1 6 gray 1 7 green 1 8 white 1 9 yellow 2 Insert nut M6 Item no 12477 5 9970 ENU Change 89188 Approved 2016 04 18 Page 4 9 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ...proval CCC CSA C22 2 No 100 EAC UL 1004 1 With regard to cyclic speed loads note that the rotating parts of the device are designed for a maximum of one million load cycles If you have special questions consult ebm papst for support 3 4 Mounting data For screw clearance see Chapter 3 1 Product drawing Secure the screws against unintentional loosening e g use self locking screws Strength class of s...

Page 6: ...rth connection circuit must be verified in the end application Depending on the circumstances of installation it may be necessary to connect an additional protective earth conductor to the extra protective earth terminal on the device 4 2 2 Voltage control With speed control using transformers or electronic voltage regulators e g phase control excessive current may occur In addition depending on h...

Page 7: ...nection Y Star connection L1 U1 black L2 V1 blue L3 W1 brown W2 yellow U2 green V2 white TOP 2x gray PE green yellow Item no 12477 5 9970 ENU Change 89188 Approved 2016 04 18 Page 7 9 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 8: ...he voltage at all poles before opening the device CAUTION The motor restarts automatically when operating voltage is applied e g after a power failure Risk of injury Keep out of the device s danger zone When working on the device switch off the line voltage and ensure that it cannot be switched back on Wait until the device comes to a stop Install the externally wired thermal overload protector in...

Page 9: ...posal of products or waste occurring in the various phases of the life cycle The corresponding disposal standards are also to be heeded 5 3 2 Disassembly Disassembly of the product must be performed or supervised by qualified personnel with the appropriate technical knowledge The product is to be disassembled into suitable components for disposal employing standard procedures for motors WARNING He...

Reviews: