ebm-papst A8D800-AN01-01 Operating Instructions Manual Download Page 5

Operating instructions

A8D800-AN01-01

Translation of the original operating instructions

3.2 Nominal data

Motor

M8D138-HF

Phase

3~

3~

Nominal voltage / VAC

400

400

Connection

Δ

Y

Frequency / Hz

50

50

Type of data definition

ml

ml

Valid for approval /
standard

CE

CE

Speed / min

-1

680

540

Power input / W

790

480

Current draw / A

2.15

1.05

Max. back pressure / Pa

100

60

Max. ambient
temperature / °C

55

55

Starting current / A

5.5

ml = max. load · me = max. efficiency · fa = running at free air

cs = customer specs · cu = customer unit

Subject to alterations

3.3 Data according to ErP directive

Installation category

A

Efficiency category

Static

Variable speed drive

No

Specific ratio

*

1.00

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

32.8

28.8

32.8

Efficiency grade N

40

36

40

Power input P

e

/ kW

0.72

Air flow q

v

/ m³/h

10375

Pressure increase total p

sf

/ Pa

81

Speed n / min

-1

685

Data established at point of optimum efficiency

3.4 Technical features

Mass

22.2 kg

Size

800 mm

Surface of rotor

Cast in aluminium

Material of terminal box

PP plastic

Material of blades

Die-cast aluminum

Number of blades

5

Blade angle

- 5

Direction of air flow

"V"

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP 54

Insulation class

"F"

Humidity class

F3-1

Mounting position

Any

Condensate discharge
holes

On rotor and stator sides

Operation mode

S1

Motor bearing

Ball bearing

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical leads

Via terminal box

Motor protection

Thermal overload protector (TOP)
brought out

Cable exit

Axial

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 60034; EN 61800-5-1; CE

Approval

VDE

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

;

Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+ 80 °C

Min. permissible
ambient motor temp.
(transp./storage)

- 40 °C

Item no. 10012-5-9970 · Revision 75933 · Release 2012-04-16 · Page 5 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for A8D800-AN01-01

Page 1: ...orised specialist personnel are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device Observe the following when working on the unit Do not make any modifications additions or conversions to the devi...

Page 2: ...loose items of clothing and jewellery could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect long hair by wearing a cap 1 7 Emission WARNING Depending on the installation and operating conditions a sound pressure level greater than 70 dB A may arise Danger of noise induced hearing loss Take appropri...

Page 3: ...n imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation with external vibrations Moving solids content in flow medium Painting the device Connections e g screws coming loose during operation Opening the terminal box during operation Moving air that contains abrasive particles Moving highly corrosive air e g salt spray ...

Page 4: ...m 1 Direction of air flow V 2 Depth of screw max 18 mm 3 Tightening torque 1 5 0 2 Nm 4 Cable diameter min 7 mm max 14 mm tightening torque 2 0 3 Nm Item no 10012 5 9970 Revision 75933 Release 2012 04 16 Page 4 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 5: ...on of rotation Clockwise seen on rotor Type of protection IP 54 Insulation class F Humidity class F3 1 Mounting position Any Condensate discharge holes On rotor and stator sides Operation mode S1 Motor bearing Ball bearing Touch current acc IEC 60990 measuring network Fig 4 TN system 3 5 mA Electrical leads Via terminal box Motor protection Thermal overload protector TOP brought out Cable exit Axi...

Page 6: ...on the customers side and can damage the device Make sure that the cable end is connected in a dry environment Connect the device only to circuits that can be switched off using an all pole disconnecting switch 4 2 1 Prerequisites Check whether the data on the type plate agree with the connection data Before connecting the device ensure that the supply voltage matches the operating voltage of the ...

Page 7: ...installed lying flat cable routed as a water trap Fans installed in upright position When routing the cable ensure that the screwed cable glands are arranged at the bottom The cables must always be routed downwards Ill 3 Cable routing for fans installed upright 4 3 4 Motor protection CAUTION Electrical voltage The device is a built in component and features no electrically isolating switch Connect...

Page 8: ...nection Y Star connection L1 U1 black L2 V1 blue L3 W1 brown W2 yellow U2 green V2 white TOP 2 x grey PE green yellow Item no 10012 5 9970 Revision 75933 Release 2012 04 16 Page 8 10 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Page 9: ... repairs may be carried out by ebm papst only The terminal box does not have to be opened for maintenance Do not perform any repairs on your device Return the device to ebm papst for repair or replacement WARNING Terminals and connections have voltage even with a unit that is shut off Electric shock Wait five minutes after disconnecting the voltage at all poles before opening the device CAUTION Th...

Page 10: ...spection At least every 6 months Replacement of the device Mounting the connection lines Visual inspection At least every 6 months Fasten Mounting of protective earth connection Visual inspection At least every 6 months Fasten Check the insulation of the wires for damage Visual inspection At least every 6 months Replace wires Tightness of screwed cable gland Visual inspection At least every 6 mont...