ebm-papst A6D800-AU01-01 Operating Instructions Manual Download Page 8

Operating instructions

A6D800-AU01-01

Translation of the original operating instructions

4.4 Connection screen

Δ

Delta connection

Y

Star connection

L1

= U1 = black

L2

= V1 = blue

L3

= W1 = brown

W2

yellow

U2

green

V2

white

TOP

2 x grey

PE

green/yellow

Item no. 10815-5-9970 · ENG · Revision 82270 · Release 2014-11-12 · Page 8 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for A6D800-AU01-01

Page 1: ...d technical staff Only authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety r...

Page 2: ...hair loose items of clothing and jewellery could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect l...

Page 3: ...prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation wit...

Page 4: ...Direction of air flow V 2 Depth of screw max 18 mm 3 Tightening torque 1 5 0 2 Nm 4 Cable diameter min 7 mm max 14 mm tightening torque 2 0 3 Nm Item no 10815 5 9970 ENG Revision 82270 Release 2014 1...

Page 5: ...es On rotor and stator sides Operation mode S1 Motor bearing Ball bearing Touch current acc IEC 60990 measuring network Fig 4 TN system 3 5 mA Electrical leads Via terminal box Motor protection Therma...

Page 6: ...eck whether the data on the type plate agree with the connection data Before connecting the device ensure that the supply voltage matches the operating voltage of the device Only use cables designed f...

Page 7: ...p Fig 2 Fan installed lying flat cable routed as a water trap Fans installed in upright position When routing the cable ensure that the screwed cable glands are arranged at the bottom The cables must...

Page 8: ...ion Y Star connection L1 U1 black L2 V1 blue L3 W1 brown W2 yellow U2 green V2 white TOP 2 x grey PE green yellow Item no 10815 5 9970 ENG Revision 82270 Release 2014 11 12 Page 8 10 ebm papst Mulfing...

Page 9: ...at all screws and screwed cable glands are properly tightened 4 7 Switch on device The device may only be switched on if it has been installed properly and in accordance with its intended use includin...

Page 10: ...diagram Thermal overload protector responded Allow motor to cool off locate and rectify cause of error if necessary cancel restart lock out Unacceptable operating point Check operating point Overtemp...

Reviews: