ebm-papst A4D500-AE03-01 Operating Instructions Manual Download Page 5

Operating instructions

A4D500-AE03-01

Translation of the original operating instructions

3.2 Nominal data

Motor

M4D110-GF

Phase

3~

3~

3~

3~

Nominal voltage / VAC

400

400

480

480

Wiring

Δ

Y

Δ

Y

Frequency / Hz

50

50

60

60

Method of obtaining
data

ml

ml

ml

ml

Valid for approval/
standard

CE

CE

CE

CE

Speed (rpm) / min

-1

1360

1110

1600

1240

Power consumption / W

690

490

1100

740

Current draw / A

1.43

0.86

1.72

1.08

Max. back pressure / Pa

160

105

215

125

Min. ambient
temperature / °C

-40

-40

-40

-40

Max. ambient
temperature / °C

90

90

55

55

Starting current / A

6.5

7.5

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to Commission Regulation (EU) 327/
2011

Actual

Req. 2015

01 Overall efficiency η

es

/ %

34.9

32.5

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

42.4

40

05 Variable speed drive

No

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart ·
HRA 590344
D-74673 Mulfingen

08 Type

A4D500-AE03-01

09 Power consumption P

e

/ kW

0.66

09 Air flow q

v

/ m³/h

5600

09 Pressure increase total p

sf

/

Pa

149

10 Speed (rpm) n / min

-1

1370

11 Specific ratio

*

1.00

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller

combination in a standardized measurement setup.

3.4 Technical description

Weight

10.2 kg

Size

500 mm

Motor size

110

Rotor surface

Cast in aluminum

Terminal box material

PP plastic

Blade material

Sheet aluminum

Number of blades

5

Blade pitch

-5°

Airflow direction

V

Direction of rotation

Counterclockwise, viewed toward rotor

Degree of protection

IP54

Insulation class

"F"

Moisture (F) /
Environmental (H)
protection class

H2

Ambient temperature
note

Occasional start-up at temperatures
between -40°C and -25°C is permitted.
For continuous operation at ambient
temperatures below -25°C (such as
refrigeration applications), use must be
made of a fan design with special low-
temperature bearings.

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Electrical hookup

Terminal box

Motor protection

Thermal overload protector (TOP) with
basic insulation

with cable

Axial

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 60034-1 (2010); CE

Approval

EAC; VDE

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

; Use the device in accordance with its degree of protection.

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. This does not however in any way affect the
technical properties of the products. The product is to be protected against
UV radiation to prevent the formation of patches and fading. Changes in
color are not a reason for complaint and are not covered by the warranty.

Item no. 13793-5-9970 · ENU · Change 98149 · Approved 2020-10-01 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for A4D500-AE03-01

Page 1: ...authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic...

Page 2: ...the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and be pulled into the dev...

Page 3: ...following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also i...

Page 4: ...ion of air flow V 2 Max clearance for screw 12 mm 3 Tightening torque 1 5 0 2 Nm 4 Cable diameter min 6 mm max 12 mm tightening torque 2 0 0 3 Nm Item no 13793 5 9970 ENU Change 98149 Approved 2020 10...

Page 5: ...m Terminal box material PP plastic Blade material Sheet aluminum Number of blades 5 Blade pitch 5 Airflow direction V Direction of rotation Counterclockwise viewed toward rotor Degree of protection IP...

Page 6: ...on serious damage can result Ensure that the device is securely positioned at its place of installation until all fastening screws have been tightened The fan must not be strained on fastening 4 2 Ele...

Page 7: ...terminal box 4 3 1 Preparing cables for connection Only strip the cable as far as necessary ensuring that the cable gland is sealed and there is no strain on the connections For tightening torques se...

Page 8: ...revent it from being switched back on NOTE Lack of motor protection Without motor protection the motor can overheat and suffer damage Connect the thermal overload protector installed in the winding Th...

Page 9: ...tion Y Star connection L1 V1 blue L2 U1 black L3 W1 brown W2 yellow U2 green V2 white TOP 2x gray PE green yellow Item no 13793 5 9970 ENU Change 98149 Approved 2020 10 01 Page 9 12 ebm papst Mulfinge...

Page 10: ...inexpert handling transportation damage and resultant imbalance or be caused by component or structural resonance Speed ranges with excessively high vibration levels and possibly resonant frequencies...

Page 11: ...nd replace it Repair of load bearing or rotating parts is not permitted Operate the fan for 2 hours at maximum speed so that any water that has ingressed can evaporate If cleaning does not eliminate v...

Page 12: ...tallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plasti...

Reviews: