ebm-papst A3G910-AU22-01 Operating Instructions Manual Download Page 4

Operating instructions

A3G910-AU22-01

Translation of the original operating instructions

3. TECHNICAL DATA

3.1 Product drawing

All measures have the unit mm.

1

Direction of air flow "V"

2

Depth of screw max. 25 mm

3

Cable diameter min. 4 mm, max. 10 mm, tightening torque 4±0.6 Nm

4

Tightening torque 3.5±0.5 Nm

Item no. 50190-5-9970 · ENG · Revision 260687 · Release 2022-06-22 · Page 4 / 14

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for A3G910-AU22-01

Page 1: ...vice to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it...

Page 2: ...tal contact Before working on the system machine wait until all parts have come to a standstill DANGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejecte...

Page 3: ...ng the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vib...

Page 4: ...Direction of air flow V 2 Depth of screw max 25 mm 3 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 4 Tightening torque 3 5 0 5 Nm Item no 50190 5 9970 ENG Revision 260687 Release 2022...

Page 5: ...tallation side the ebm papst evaluation loses its validity conformity must be confirmed again The product does not fall within the scope of Regulation EU 2019 1781 due to the exception specified in Ar...

Page 6: ...ed output of the arrangement 4 CONNECTION AND START UP 4 1 Connecting the mechanical system CAUTION Cutting and crushing hazard when removing the fan from the packaging Carefully remove the device fro...

Page 7: ...e installation situation it may be necessary to connect an additional protective earth conductor by way of the extra protective earth terminal provided on the device The protective earth terminal is l...

Page 8: ...f delivery into the terminal box First connect the PE protective earth connection Connect the lines to the corresponding terminals Use a screwdriver to do so During the connection work ensure that no...

Page 9: ...ich the device is pre set by ebm papst Control mode parameter set 1 PWM controlling Control mode parameter set 2 PWM controlling Fan device adress 01 Max PWM 100 Min PWM 5 Save set value to EEPROM Yes...

Page 10: ...ontact common connection contact rating 250 VAC max 2 A AC1 min 10 mA KL2 3 NC Status relay floating status contact break for failure KL 3 1 RSA Bus connection RS 485 RSA MODBUS RTU SELV KL 3 2 RSB Bu...

Page 11: ...OM setting the controller function of the integrated controller is normally inversely selectable per bus or per digital input Din 3 normal open pin or applied voltage 5 50 VDC inverse bridge to GND or...

Page 12: ...d off via power supply Switching off the device for maintenance work Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect...

Page 13: ...other problems contact ebm papst 6 1 Cleaning To ensure a long service life the fans have to be regularly checked for proper operation and degree of soiling The frequency of the checks is to be adapte...

Page 14: ...of the product and its components 6 3 1 Country specific legal requirements NOTE Country specific legal requirements Always observe the applicable country specific legal regulations with regard to th...

Reviews: