Operating instructions

A3G450-AC28-51

Translation of the original operating instructions

Motor does not turn

Mechanical blockage

Switch off, de-
energise, and
remove mechanical
blockage.

Mains supply voltage
faulty

Check mains supply
voltage,
restore power
supply,
apply control signal.

Faulty connection

De-energise, correct
connection, see
connection diagram.

Overtemperature of
electronics/motor

Insufficient cooling

Improve cooling. Let
the device cool down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.

Thermal overload
protector responded

Allow motor to cool
off, locate and rectify
cause of error, if
necessary cancel
restart lock-out

Ambient temperature
too high

Reduce the ambient
temperature.
Reset by reducing
control input to 0.

Unacceptable
operating point

Correct the operating
point. Let the device
cool down.

If you have any other problems, contact ebm-papst.

6.1 Cleaning

To ensure a long service life, the fans have to be regularly checked for
proper operation and degree of soiling. The frequency of the checks is to
be adapted to the occurrence of soiling.

DANGER
Risk of injury from rotating fan.

→ Only clean when not in motion. Do not disconnect the fan

from the power supply, just switch it off via the control input.
This will prevent start-up of the fan.

;

Dirt deposits on the motor housing could lead to overheating of the
motor.

;

Dirt on the impeller can cause vibration which would shorten the
service life of the fan.

;

Severe vibration could destroy the fan.

;

In such cases immediately switch off and clean the fan.

;

The preferred method of cleaning is dry cleaning, e.g. using
compressed air.

;

Use is never to be made of corrosive cleaning agents!

NOTE
Damage to the device during cleaning

Malfunction possible

→ Do not clean the device using a water jet or high-pressure

cleaner.

→ Do not use any acid, alkali or solvent-basedcleaning

agents.

→ Do not use any pointed or sharp-edged objects for cleaning

;

Completely remove any cleaning agents used.

;

Immediately switch off and replace the device if severe corrosion is
apparent at load-bearing or rotating parts.

;

Repairs to load-bearing or rotating parts are not permissible!

;

Operate the fan for 2 hours at maximum speed to permit the
evaporation of any water which may have ingressed.

;

If cleaning does not eliminate vibration, the fan may have to be re-
balanced. In such cases please contact ebm-papst.

;

The fan is provided with maintenance-free ball bearings. The lifetime
lubrication of the ball bearings is designed for a service life of 40,000
hours.

;

Please contact ebm-papst if bearing replacement is required after this
period.

;

Adapt the maintenance intervals to the dust pollution occurring.

6.2 Safety test

NOTE
High-voltage test

The integrated EMC filter contains Y capacitors. Therefore, the
trigger current is exceeded when AC testing voltage is applied.
→ Test the device with DC voltage when you carry out the

high-voltage test required by law. The voltage to be used
corresponds to the peak value of the AC voltage required by
the standard.

What has to
be tested?

How to test?

Frequency

Which
measure?

Check the
protective
casing against
accidental
contact for
damage and to
ensure that it is
intact

Visual inspection At least every

6 months

Repair or
replacement of
the device

Check the
device for
damage to
blades and
housing

Visual inspection At least every

6 months

Replacement of
the device

Mounting the
connection lines

Visual inspection At least every

6 months

Fasten

Mounting of
protective earth
connection

Visual inspection At least every

6 months

Fasten

Check the
insulation of the
wires for damage

Visual inspection At least every

6 months

Replace wires

Condensate
discharge holes
for clogging, as
necessary

Visual inspection At least every

6 months

Open bore holes

Weld seams for
crack formation

Visual inspection At least every

6 months

Replace device

Item no. 50718-5-9970 · ENG · Revision 225336 · Release 2020-12-03 · Page 11 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for A3G450-AC28-51

Page 1: ...evice to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once i...

Page 2: ...installations on the customer s side Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be...

Page 3: ...and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also include vibrations that are transmitted from...

Page 4: ...1 Direction of air flow V 2 Thread reach 8 10 mm 3 Connection line PVC AWG18 5x core end sleeve 4 Connection line PVC AWG22 3x core end sleeve Item no 50718 5 9970 ENG Revision 225336 Release 2020 12...

Page 5: ...he ErP data is determined using a motor impeller combination in a standardised measurement configuration 3 4 Technical features Mass 4 8 kg Size 450 mm Motor size 84 Surface of rotor Coated in black M...

Page 6: ...it by the centre of the blades only Make sure to avoid any shock Wear safety shoes and cut resistant safety gloves CAUTION The blades of the impeller could be damaged Set down the fan carefully on a...

Page 7: ...sured even when the motor is at a standstill and the mains voltage is switched on The values are typically in the range 250 mA At the same time the effective power in this operating state operational...

Page 8: ...nwards 4 4 Factory settings Factory settings with which the device is pre set by ebm papst Operation mode PWM controlling Group adress 01 Fan device adress 01 Max PWM 100 Min PWM 0 Save set value to E...

Page 9: ...inal operating instructions 4 5 Connection screen Item no 50718 5 9970 ENG Revision 225336 Release 2020 12 03 Page 9 12 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49 0 7938 81...

Page 10: ...sure to disconnect the earth wire connection last 5 INTEGRATED PROTECTIVE FUNCTIONS The integrated protective functions cause the motor to switch off automatically in case of faults described in the t...

Page 11: ...for cleaning Completely remove any cleaning agents used Immediately switch off and replace the device if severe corrosion is apparent at load bearing or rotating parts Repairs to load bearing or rota...

Page 12: ...components are heavy These components could drop off during disassembly This can result in fatal or serious injury and material damage Secure components before unfastening to stop them falling 6 3 3 C...