ebm-papst A2E300-AC50-09 Operating Instructions Manual Download Page 5

Operating instructions

A2E300-AC50-09

Translation of the original operating instructions

3.2 Nominal data

Motor

M2E068-EC

Phase

1~

1~

Nominal voltage / VAC

230

230

Frequency / Hz

50

60

Method of obtaining
data

fa

fa

Valid for approval/
standard

CE

CE

Speed (rpm) / min

-1

2700

3000

Power consumption / W

160

215

Current draw / A

0.70

0.94

Capacitor / µF

5

5

Capacitor voltage / VDB

400

400

Max. back pressure / Pa

120

140

Min. ambient
temperature / °C

-25

-25

Max. ambient
temperature / °C

90

65

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to Commission Regulation (EU) 327/
2011

Actual

Req. 2015

01 Overall efficiency η

es

/ %

29.8

29

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

40.8

40

05 Variable speed drive

No

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart
· HRA 590344
D-74673 Mulfingen

08 Type

A2E300-AC50-09

09 Power consumption P

e

/ kW

0.17

09 Air flow q

v

/ m³/h

1710

09 Pressure increase total p

sf

/

Pa

113

10 Speed (rpm) n / min

-1

2610

11 Specific ratio

*

1.00

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller

combination in a standardized measurement setup.

3.4 Technical description

Weight

2.7 kg

Size

300 mm

Motor size

68

Rotor surface

Painted black

Blade material

Sheet steel, painted black

Number of blades

5

Airflow direction

A

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP44; installation- and position-dependent
as per EN 60034-5

Insulation class

"F"

Moisture (F) /
Environmental (H)
protection class

H1+

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

< 0.75 mA

Motor protection

Thermal overload protector (TOP)
internally connected

with cable

Variable

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 60335-1; CE

Approval

UL 1004-1; CSA C22.2 No. 100

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. This does not however in any way affect the
technical properties of the products. The product is to be protected against
UV radiation to prevent the formation of patches and fading. Changes in
color are not a reason for complaint and are not covered by the warranty.

Item no. 14016-5-9970 · ENU · Change 204653 · Approved 2020-01-22 · Page 5 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for A2E300-AC50-09

Page 1: ...y qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic...

Page 2: ...efore working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and be pul...

Page 3: ...ing the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan from the customer...

Page 4: ...mm 1 Direction of air flow A 2 Max clearance for screw 6 mm 3 Cable PFA AWG18 1x crimped splice cable PFA AWG20 3x crimped splices Item no 14016 5 9970 ENU Change 204653 Approved 2020 01 22 Page 4 11...

Page 5: ...3 4 Technical description Weight 2 7 kg Size 300 mm Motor size 68 Rotor surface Painted black Blade material Sheet steel painted black Number of blades 5 Airflow direction A Direction of rotation Clo...

Page 6: ...ge on the device Electric shock Always connect a protective earth first Check the protective earth DANGER Faulty insulation Risk of fatal injury from electric shock Use only cables that meet the speci...

Page 7: ...between the drive and the motor During operation with variable frequency drives an all pole sine filter protects the motor against high voltage transients that can destroy the coil insulation system a...

Page 8: ...ctions 4 4 Connection diagram U1 blue Z brown U2 black PE green yellow Item no 14016 5 9970 ENU Change 204653 Approved 2020 01 22 Page 8 11 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen...

Page 9: ...MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Send the device to ebm papst for repair or replacement WARNING Live terminals and connections even with...

Page 10: ...ng the protective earth terminal Visual inspection At least every 6 months Fasten Insulation of cables for damage Visual inspection At least every 6 months Replace cables Condensation drainage holes f...

Page 11: ...aterials and are therefore to be treated in the same manner The materials concerned are as follows Miscellaneous insulators used in the terminal box Power cables Cables for internal wiring Electrolyti...