Operating instructions

K3G500-PB24-03

Translation of the original operating instructions

4.5 Connection diagram

No.

Conn.

Designation

Function/assignment

CON1

-

L1, L2, L3

Supply connection, power supply, protection class 1

PE

-

PE

Ground connection, PE connection

CON2

-

RSA

Bus connection RS485, RSA, MODBUS-RTU; SELV

CON2

-

RSB

Bus connection RS485, RSB, MODBUS-RTU; SELV

CON2

-

GND

GND reference ground for control interface, SELV

CON2

-

IO1

IN2: Digital input - positive logic (factory setting: Enable)
function parameterizable, SELV
- normal: Pin open or applied voltage < 1.5 VDC
- inverse: applied voltage 3.5-50 VDC

CON2

-

IO2

IN1: Analog input 0-10 V
0-10 V, Ri=100 K, parameterizable as set value or measured value (factory setting: set value)
characteristic curve parameterizable, SELV

CON2

-

IO3

OUT1: Analog output 0-10 V
0-10 V, max 5 mA, function parameterizable (factory setting: modulation level)
max output frequency 300 Hz, SELV

CON2

-

V out

Voltage output 3.3-24 VDC +/-5%, Pmax=800 mW, voltage parameterizable (factory setting: 10 VDC)
short-circuit-proof, supply for external devices, SELV
alternatively: 15-50 VDC input for parameterization via Modbus without line voltage

CON2

-

COM

Status relay, floating status contact; common connection, nominal voltage 250 VAC; max 2 A (AC1): min 10
mA; Reinforced insulation in accordance with EN60335-1, EN61800-5-1, UL60730-1

CON2

-

NC

Status relay, floating status contact, break for failure

Item no. 55783-5-9970 · ENU · Change 99204 · Approved 2018-08-01 · Page 9 / 14

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Summary of Contents for K3G500-PB24-03

Page 1: ...evice to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again fo...

Page 2: ...rical or electromagnetic interference after installing the device in customer equipment Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to b...

Page 3: ...n stationary systems Performing all maintenance work Conveying air at an ambient air pressure between 800 mbar and 1050 mbar Using the device within the permitted ambient temperature range see Chapter...

Page 4: ...ustrated or rotor on bottom rotor on top on request 2 Cable diameter min 4 mm max 10 mm tightening torque 2 0 3 Nm 3 Tightening torque 1 5 0 2 Nm 4 Inlet ring with pressure tap k factor 281 5 Mounting...

Page 5: ...ion in a standardized measurement setup 3 4 Technical description Weight 43 3 kg Size 500 mm Motor size 150 Rotor surface Painted black Electronics housing material Die cast aluminum Impeller material...

Page 6: ...he network operator that this device is only connected to a connection point with a Ssc value that is greater than or equal to 120 times the rated output of the arrangement 4 CONNECTION AND STARTUP 4...

Page 7: ...necessary to connect an additional protective earth conductor by way of the extra protective earth terminal provided on the device The protective earth terminal is located on the housing and provided...

Page 8: ...s Use a screwdriver to do so When connecting ensure that no wire ends fan out Seal the terminal box 4 3 3 Cable routing Water must be prevented from reaching the cable gland along the cable NOTE Damag...

Page 9: ...tting set value characteristic curve parameterizable SELV CON2 IO3 OUT1 Analog output 0 10 V 0 10 V max 5 mA function parameterizable factory setting modulation level max output frequency 300 Hz SELV...

Page 10: ...nput Ri 100K characteristic curve parameterizable fPWM 1k 10KHz SELV D159 2 Ain2 4 20mA analog input Ri 125R characteristic curve parameterizable SELV D159 3 Din3 active high digital input not active...

Page 11: ...nce from inexpert handling transportation damage and resultant imbalance or be caused by component or structural resonance Speed ranges with excessively high vibration levels and possibly resonant fre...

Page 12: ...wn Ambient temperature too high Reduce the ambient temperature Allow the device to cool down Impermissible operating point e g back pressure too high Correct the operating point Allow the device to co...

Page 13: ...of cables for damage Visual inspection At least every 6 months Replace cables Impeller for wear deposits corrosion and damage Visual inspection At least every 6 months Clean impeller or replace devic...

Page 14: ...lating materials Cables and wires Electronic scrap e g circuit boards Only ferrite magnets and not rare earth magnets are used in external rotor motors from ebm papst Mulfingen GmbH Co KG Ferrite magn...

Reviews: