background image

c/c-space 25

46 cm

Cold cable Splice (is to be fully grouted)

Endseal

Plug

Planning & Installing

Layout

1.  Keep heating coil in heated area. The installation will then be easier.
2.  Roll out the cable on the bottom reinforcement.
3.  Lash loosely. Use tape or plastic-coated lash thread. Machine can be used with loose settings.
4.  The cables must not be crossed. Minimum spacing between cables 15 cm.
5.  Warning! The cable is not to be in contact with non-conducting composition as cellular plastic, mineral 

wool, or similar.

6.  The whole heating cable length is to be moulded in, including the cold cable splice.
7.  The cable is to be taken in use immediately after moulding. (Before moulding, you must only connect 

the cable for short time tests).

Installation instructions BHS

Heating cable for hardening/frost protection of concrete

EN

Calculating the area and cable spacing when curing concrete

Plan the surface on the basis of your required output/m2. Try to keep the connection ends close 

to each other. If the central BHS unit is used, the spiral hose (item no. 8960541) has to be attached 

between two heat cables and in the centre of the cast concrete. It is used for the sensor cable.

Cable length

85 m

55 m

35 m

20 m

10 m

Effect (W/m2)

Area m2 c/c

Area m2 c/c

Area m2 c/c

Area m2 c/c

Area m2 c/c

150

23

27

15

27

9

27

5

25

2,5

25

120

29

34

19

34

12

34

6

30

3,2

32

100

35

41

22

40

14

40

7

35

3,8

38

90

39

46

25

46

16

46

8

40

4,2

42

Summary of Contents for BHS

Page 1: ...allkabelskarven 7 Kabeln tas i drift omedelbart efter gjutning f re gjutning f r tillslag ske endast kortvarigt f r test c c avst nd 25 46 cm Kallkabelskarv skall gjutas in ndavslut Anslutningsdon Pla...

Page 2: ...aptern art nr 2403033 f r att enkelt g ra seriekopplingen Uttorkning Kabell ngd Effekt Sp nning 2x85 m 1750 W 875 W slinga 230 V 2x55 m 1100 W 550 W slinga 230 V 2x35 m 700 W 350 W slinga 230 V 2x20 m...

Page 3: ...e is to be taken in use immediately after moulding Before moulding you must only connect the cable for short time tests Installation instructions BHS Heating cable for hardening frost protection of co...

Page 4: ...e output is utilised The series connection adapter art no 2403033 allows this to be done in a simple way Drying Cable length Effect Voltage 2x85 m 1750 W 875 W cable 230 V 2x55 m 1100 W 550 W cable 23...

Page 5: ...ekabellengden skal st pes inn inkl kaldkabelskj ten 7 Kabelen tas i drift umiddelbart etter st pning f re st pning kan pr ving kun skje kortvarig for test c c avstand 25 46 cm Kaldkabelskj t skal st p...

Page 6: ...pter art nr 2403033 for enkel seriekobling Utt rking Kabellengde Effekt Sp nning 2x85 m 1750 W 875 W slinga 230 V 2x55 m 1100 W 550 W slinga 230 V 2x35 m 700 W 350 W slinga 230 V 2x20 m 370 W 185 W sl...

Page 7: ...iitosjohtojatkos 7 Kaapeli kytket n p lle v litt m sti valun tapahduttua ennen valua saa kaapelin kytke p lle vain lyhytaikaisesti mahdollista tarkistusta varten k k et isyys 25 46 cm Liitosjohtojatko...

Page 8: ...okaapelin kanssa Suunnittelu ja asennus Piitus Teho J nnite 2x85 m 1750 W 875 W kieppi 230 V 2x55 m 1100 W 550 W kieppi 230 V 2x35 m 700 W 350 W kieppi 230 V 2x20 m 370 W 185 W kieppi 230 V 2x10 m 35...

Reviews: