EBARA E-SPD Series Instruction And Maintenance Manual Download Page 22

22

EN

ALARM F02
SHORT CIRCUIT

The motor is communicated or has 

burnt out.

Not all wires have been connected.

Internal fault in the frequency converter.

Disconnect the motor from the frequency 

converter and check that the message 

disappears. If this is not the case, contact 

your nearest technical service.
Check that all the cables of the motor are 

correctly connected to the motor itself 

and also to the frequency converter. 

Also supervise the correct wiring of the 

frequency converter’s power supply.
Contact your nearest technical service.

ALARM F03
EXCESS TEMPERATURE
OF THE MODULE

The power module has reached a very 
high temperature, compromising its 
reliability.

Ensure the ambient temperature does 

not exceed the extremes set out in this 

manual.
If it is assembled on the pump, ensure 

the pump has a fan and that the fan 

cover has been fitted.
If it is assembled on a wall mount, 

ensure the fan of the mount functions 

correctly when the motor is running.

ALARM F04
INPUT
VOLTAGE

The frequency converter is not receiving 
electric current, of is outside of the upper 
and lower limits.

The electrical supply to the frequency 

converter has been interrupted.
The electrical connection cable from 

the mains electricity to the frequency 

converter has been disconnected.
The electrical voltage entering the 

frequency converter is outside the limits 

specified in the technical data section.

ALARM F05
TRANSDUCER

The frequency converter does not 
receive a correct reading from the 
pressure transducer.

The pressure transducer is wired in the 

frequency converter with the polarity 

reversed.
The pressure transducer is broken.
The pressure transducer has a range 

other than 4-20 mA.

MESSAGE

REASONS

SOLUTION(S)

ALARM F01
OVERCURRENT

Indicates excessive consumption in the 
motor.

Check that the nominal consumption 
data has been entered correctly.
Check that the pump rotates freely with 
no obstructions.

15. ALARMS

Summary of Contents for E-SPD Series

Page 1: ...QL L vQWUH LQHUH 423 RO XOODQ P YH EDN P N ODYX X 451 TR 3 25 47 69 91 113 135 157 179 201 223 INVERTER FOR PUMPS Instruction and maintenance manual INVERTER PER ELETTROPOMPE Manuale di istruzioni e m...

Page 2: ......

Page 3: ...on and assembly 8 Electrical connections 9 Screen format 10 Main screen 11 Operation mode 12 Start upwizard 13 Setup menu 14 Warning management 15 Alarms 16 Maintenance and repair 17 Warranty 18 Dispo...

Page 4: ...al sensory or mental capabilities or without the due experience or knowledge except if a person responsible for their safety has explained the instructions and supervised their operation of their freq...

Page 5: ...ts of use Minimum ambient temperature 10 C Maximum ambient temperature 40 C Variation in the supply voltage 10 Humidity range 5 to 95 without condensation and vapor Maximum altitude 2 000 meters The a...

Page 6: ...according to the regulations in force in the country in question A table with the maximum recommended lengths according to the cross section of the electrical cable can be found below Each interface c...

Page 7: ...rt adapter parts 5 and 11a provided Break the 3 holes of the metal radiator of the power circuit part 4 with a screwdriver The 3 holes are visible on the inside of the radiator add the image Screw the...

Page 8: ...485 COMUNICATION FRONT PANEL U V W TT3 MT2 MOTOR 230 400Vac MOTOR 230 400Vac MT2 230Vac 1 N R POWER SUPPLY TT3 400Vac 3 S T 8 ELECTRICAL CONNECTIONS B A B A E SPD MT 2200 E SPD TT 4000 It is necessary...

Page 9: ...requency converter is giving a voltage output its maximum load is 9 W You can connect any potential free contact that will perform the functions programmed in parameters 5 12 and 5 13 respectively to...

Page 10: ...isplay Manual stop button Right selection button Lower button Raise button Left selection button Alarm LED H z 4 8 9 4 8 8 A m p 0 8 3 0 8 9 B a r 0 5 5 0 5 5 1 4 5 7 M e n u Current rotation frequenc...

Page 11: ...stablished working pressure In contrast when the demand for flow decreases the frequency converter makes the electric motor rotate more slowly so the pressure of the water network remains unaffected b...

Page 12: ...ase the value that is blinking and use F2 to change to the next value The sequence of values is DAY MONTH YEAR HOUR MINUTES The lower left part of the display indicates the day of the week calculated...

Page 13: ...e is always within the working curve of the pump and always try to avoid the extremes of the curve in other words with flows near 0 or very low pressures Validate this with F2 F2 Once you have reached...

Page 14: ...ot be displayed The stop frequency calculated is indicated this is for the working pressure indicated when the pump drops below this frequency it does not generate any flow so the motor then stops Pre...

Page 15: ...7 MINIMUM WORKING FREQUENCY 5 08 MAXIMUM WORKING FREQUENCY 5 09 AUXILIARY OPERATING FREQUENCY 5 10 MINIMUM AUXILIARY OPERATING DELAY 5 11 MINIMUM AUXILIARY STOP DELAY 5 12 DIGITAL INPUT 1 5 13 DIGITAL...

Page 16: ...onnected to an electricity grid 2 04 HOURS WORKED Hours This indicates the total number of hours worked providing an output voltage of the frequency converter 2 05 START UP NUMBER This indicates the t...

Page 17: ...00 5 06 PRINCIPAL STOP DELAY Sec Time from the moment the main pump is working at a speed below the stop frequency parameter 1 4 until it stops fully ATTENTION Improper use of manual mode can cause ov...

Page 18: ...remotely OFF The relay is never activated Alarm NO The relay closes before an alarm Alarm NC The relay opens before an alarm Running The relay is energised when the unit is running External stop The r...

Page 19: ...after the 24 hour notice is detected again dry running the drive will lock indefinitely until you press F2 5 1 99 5 23 LOW WATER LEVEL ALARM DELAY Sec Time from when the system calculates a low water...

Page 20: ...he RUN LED blinks The frequency converter is in the process of stopping the pump WARNING REASON EXPLANATION SOLUTION 14 WARNING MANAGEMENT One of the main principles of the frequency converter is to t...

Page 21: ...ng the stop frequency setup wizard again 5 24 If this warning persists after running the wizard again you must reduce the working pressure as the pump that is connected will not be able to reach it Th...

Page 22: ...it is assembled on a wall mount ensure the fan of the mount functions correctly when the motor is running ALARM F04 INPUT VOLTAGE The frequency converter is not receiving electric current of is outsi...

Page 23: ...ng at a very low pressure and at a speed high for a time Check that the water network has no leaks greater than those required for regular demand ALARM A10 TIME PARAMETERS The stop delays of the auxil...

Page 24: ...r from any liability in case of accidents to people or damage to property and or to the product itself Once the product has been received check that it has not suffered significant breaks or dents Oth...

Reviews: