CD200 OWNERS MANUAL
Drawing No. :- TPC364
Issue
:- 7
Date
:- 10/12/13
External Humidistat Option
The CD200 has the option of using an external humidistat remotely mounted within a room,
where available.
In the control box there is a connector that can be wired to, which will enable the use of an
external humidistat. The following steps should be carried out to enable correct operation of
the external humidistat.
•
Locate the control box and remove the cover, keeping screws for re-attachment
•
Locate the connector within the control box and remove the plug from the socket
•
Dismantle the plug and remove the link wire from terminals 2 & 3
•
Wire remote humidistat to terminals 1 & 3, ensuring wires pass through the plug back shell
•
Re-assemble the plug and refit to the socket on the control box
•
The CD200 internal humidistat will now be by-passed and the external humidistat will
control the unit.