2. Installation
2.9 Preparing the device for operation
Specifications for connection to 24 VDC supply voltage
min. AWG18 / max. AWG12
Tightening torque
0.6 ... 0.8 Nm (5 ... 7 lb-in)
for the screws on the Plug connector MSTB 2.5/3-ST-5.08
Strip length
7 mm
Power supply
+24 V DC
0 V
U
e
= 24 V DC
(19.2 - 30 V DC SELV)
I
e
= ...
0 V +24 V DC
0.6 - 0.8 Nm
(5 - 7 lb-in)
Fig. 15: Connecting the screw terminals on the Plug connector MSTB 2.5/3-ST-5.08
Electrical connection
0 V
+24 V DC
Fig. 16: Power supplied through Plug connector MSTB 2.5/3-ST-5.08
Use the Plug connector MSTB 2.5/3-ST-5.08 to terminate the connection cable for
the power supply in advance.
Plug the pre-assembled plug into the socket on the enclosure.
Pay attention to the polarity "+24V" and "0V".
Connect the power supply cable to a 24 VDC supply voltage that meets the requi-
rements for safety extra-low voltages (SELV) set forth in IEC 60950 and – in
connection with the UL listing – the requirements for a low-voltage source set
forth in UL 61010-2-201.
The XV360 Single Touch Display is now ready to run on 24 V
DC
.