7 Maintenance and service
7.4 Troubleshooting
46
MICRO PANEL XV-112
11/2011 MN04802005Z-EN
www.eaton.com
7.4
Troubleshooting
Tab. 17 Troubleshooting
Fault and possible cause
Corrective action
Device does not start (boot).
Power supply interface does not have any
power.
Check the power supply cable.
While the device is starting (booting), the following
message appears:
«<50> Touch is dirty or defect»
(only appears if GALILEO is installed)
Resistive touch is not correctly calibrated.
Start (boot) the device.
Calibrate touch
(
→
Document «MN05010007Z-EN System
Device is faulty.
Send in your device for repair.
Display remains or becomes dark.
Backlight is switched off.
Check the function in the visualization software.
Backlight is faulty.
Send in your device for repair.
Touch does not react or does not react correctly to
touch operation.
Resistive touch is not correctly calibrated.
Start (boot) the device.
Calibrate touch
(
→
Document «MN05010007Z-EN System
Touch is deactivated.
Start (boot) the device.
Activate touch
(
→
Document «MN05010007Z-EN System
The icon
appears in the taskbar.
Incorrect operation of the operating elements
on the display.
Remove all objects from the area of the display.
Device is faulty.
Send in your device for repair.