EATON XSTORAGE COMPACT INSTALLATION MANUAL
P-16400097 - September 2020 www.eaton.com
31
5.4.3
Minimum recommended fuse sizes
Table 8. AC input fuse and MCB ratings*
xStorage Compact
rating (kW/kVA)
10
20
30
40
Fuse / MCB rating
[A]
20
40
63
80
*Fuses are of the type gG and MCB tripping characteristics C.
5.5
Install a remote EPO switch
You can use a remote EPO switch in case of an emergency to shut down the ESS and remove power to
the critical load from a location away from where the ESS is installed.
EPO is connected to the ESS’s top front panel, on connector EPO. Figure 13: Connections of the EPO
switch shows the NO and NC connections of the EPO switch.
EPO connector (front view):
•
A = Normally open
•
B = Normally closed
Figure 13. Connections of the EPO switch
5.6
Communication interface connections
This section describes all xStorage Compact ESS communication interface connections. Terminal blocks
are located in the communication area, in the upper section of the unit (see
Figure 14. Communication
interfaces
).